Addressing BACS Modules 

 

Pressing  „

Start

“  in  the  Programmer  increases  the 

frequency  of  the  red  flashing  lights  on  the 

BACS 

modules

. The modules are ready for registration  

 
 
Press  the  button  on  the 

BACS  module 

briefly  with 

the  BACS  PEN.  The  module  signals  the  successful 
addressing with a green light signal. Repeat until all 
modules flash green. 
 

Attention: 

In  automatic  addressing  mode,  all  LEDs  must  flash 
rapidly  in  red.  If  this  does  not  happen,  there  is  a 
problem with the modules.  
 

If  it  happens, set the "

Set  all address  to  0

" checkbox 

at  the  programmer.  You  can  also  press  and  hold  the 
button  on  the  relevant  BACS  module  for  about  10  se-
conds  to  reset  the  module  to  the  delivery  state  (With 
C20  HW  3.x,  FW  3.4.1  and  C30  &  C40  HW  3.x  from 
FW  3.4.2,  this  BACS  module  function  is  no  longer 
available). After that restart registration process. 
 
 
 
 

Final Conditions of  
Module Addressing 

 

The automate addressing progress bar:

 

With  each  module  registration,  the  BACS 

Program-

mer 

will  count  1  up  until  the  indicated  number  of 

modules are  registrated. 
 
 

All indicated module addresses are used  

 

The 

BACS WEBMANAGER 

terminates the registra-

tion process and reports a successful registration. 

 
 

The last module has been registrated 

 

If  you specified  more modules  than  are  actually instal-
led,  you  can  stop  the  progress  manually.  Click  on  the 

Stop

“ button. 

 
 
Please note: 

 

In  both  cases  the  status  LED  of  the  modules  must 
be green or flash green. 

Summary of Contents for BACS System

Page 1: ...Components BACS Measuring Cable BACS Bus Cable BACS Module BACS WEBMANAGER CS141 SNMP Adapter Professional BACS Bus Converter BACSKIT_BSC4 Slot Version BACSKIT_LB4 External Box CS141 SNMP Adapter MODB...

Page 2: ...with EN 50272 2 2001 Safety Re quirements for Secondary Batteries and Battery Installations Part 2 Stationary Batteries IEEE Standard 450 2002 Recommended Practice for Maintenance Testing and Replace...

Page 3: ...s after a discharge period BACS modules must NOT be mounted on a damaged battery If a battery is damaged and its internal resistance is high charging current or current being discharged may follow the...

Page 4: ...time frame for reaction to alarms BACS is a tool designed to increase the durability of accumulators but its most important function is to monitor the battery in order to avoid breakdowns For this rea...

Page 5: ...ry the surface of the ac cumulator with an antistatic fabric 1 2 Installation BACS Measuring Cables Please follow the installation diagrams on the next pages to mount the cables correctly to the batte...

Page 6: ...BACS test lead to all poles Note If the battery has more than 4 poles it is sufficient to connect the BACS cable to four battery poles Use the same poles at each battery Note Please refer to the batte...

Page 7: ...Order No BACSC23 Order No BACSC30 Order No BACSC40 Order No BACSC41 Order No BACSC50 As standards BACS modules are equipped with integrated temperature Optional you can get the Module with an externa...

Page 8: ...cooling ribs or plugs Wet cells For wet cells and low maintenance batteries ensure a clearance to the breather of at least 10 cm 3 94in BACS Modules with external temperature sensors Instead of the i...

Page 9: ...e Velcro strips 2 Mounting the BACS module Position the BACS module press it firmly with your thumb under high pressure and hold the pressure for about 5 10 seconds Connecting BCx Measuring Cable to t...

Page 10: ...maximum of 50 connected modules The modules can be connected to the bus in any order It is not necessary to connect the modules of the addresses in sequence Connection to the BACS WEBMA NAGER BACS Bus...

Page 11: ...4 Max cable length from BACS WEBMANAGER to BACS SPLITTING BOX should not exceed 10m 395in Otherwise it will reduce the max length of 6 5 The cable length of the connection between the BACS SPLITTING...

Page 12: ...en the distance of 50m 1970in 8 Max number of BACS Modules is 512 9 Max distance from BACS WEBMANAGER to BACS CURRENT SENSORs should not exceed 10m 395in 10 Max distance between the BACS_GX_R_AUX and...

Page 13: ...ER MODBUS RS485 CS141SCM Slot external BACS Bus Converter Order No BACSKIT_SCMB4 SNMP WEB MANAGER MODBUS RS485 CS141LM external external BACS Bus Converter Order No BACSKIT_LMB4 The BACS Bus Converter...

Page 14: ...generex us Wiring instruction BACS WEBMANAGER BACS WEBMANAGER BACS Kit Box with external BACS Bus Converter BACS Bus cables Power Supply BACS BUS Special cable RJ12 BACS BUS Power Supply Power Supply...

Page 15: ...allows an optimized star shaped bus cabling instal lation It is possible to connect more BACS SPLIT TING BOX at one BACS System Distribute all BACS modules equally to the ports of the SPLITTING BOX E...

Page 16: ...Converter BACS Buskabel BACS Bus cable BACS WEBMANAGER Budget with BACS SPLITTING BOX Installation of the BACS hardware complete For operational mode the BACS modules need to be configured BACS Bus ca...

Page 17: ...12 6pole cable 6 LEDs red green Operation Status WEBMANAGER Red LED Green LED No Power OFF OFF Booting ON OFF Update in progress flashing slowly OFF Update failure flashing fast OFF UPS Communication...

Page 18: ...PS cable to the COM1 port of the web manager Connecting the BACS WEBMANAGER directly with a UPS system is an additional feature BACS will run without it too when using a BACS WEBMANAGER Slot card vers...

Page 19: ...141 snmp 2 4 Run the Setup Wizard On very first login the Webmanager will start a tool that will help you with the basic configuration System Setup Wizard The Setup Wizard will guide you through the m...

Page 20: ...f you want to use BACS only select No UPS model defined 3 4 Press Apply to save your settings Configure the local system time The time is important for accurate event logging 1 Under System go to Date...

Page 21: ...pply or insert the slot card into the according slot of the UPS 4 Connect the Webmanager to your local network The UPS will continue running as expected Remo ving the power supply from the external CS...

Page 22: ...they are connected to the measuring cable They wake up automatically if the BACS WEBMANAGER BACS Programmer or BACS Reader sends request To wake up the modules it s necessary to activate bus communic...

Page 23: ...er tap using a configuration like that you need to setup your BACS system according to it To handle different power circuits your BACS confi guration needs for each power circuit an indepen dent strin...

Page 24: ...earch Tool Find BACS modules by address 4 2 1 Addressing BACS Modules via Automatic Mode Automatic mode allows automatic addressing of modules After each successful addressing an address is automatica...

Page 25: ...can also press and hold the button on the relevant BACS module for about 10 se conds to reset the module to the delivery state With C20 HW 3 x FW 3 4 1 and C30 C40 HW 3 x from FW 3 4 2 this BACS modu...

Page 26: ...to provide the replacement of broken mo dules as well as adding one single module to the existing configuration Please Ensure only one module is connected to your Manager Entering address Under Old en...

Page 27: ...dialog as expected 1 Remove the power supply from the WEBMANAGER For the slot versions pull the card out of the slot of your UPS 2 To switch the WEBMANAGER to operating mode left position manual IP ri...

Page 28: ...ccessful initialization the BACS status page will be displayed with the voltage and temperature of the batteries the equalization power and the status of the LEDs After approximately 15 minutes the fi...

Reviews: