3.6.2 Connecting load cable
The generator set is ready for user connections. The user load cable should be
connected to the corresponding wire terminal which is located inside the
control cabinet or switch cabinet, then use a wrench to tighten cable
connections and fix them.
Power cables must be placed in suitable channel, tunnels or protective
conduct-holder. Do not include AC and DC cables in the same channeling.
WARNING
Connection must be carried out only by a licensed electrician.
3.7 Ground connections
Metal parts of installation, which are exposed to human or have insulation flaw
or other reasons, may get in contact with voltage. There must be connected to
the ground.
The generator and its electrical components have been equipped with their
correspondent grounding terminals, all connected to a ground strip of the
generator power cabinet. This strip is connected to the grounding terminal that
is in the frame base. Connect the ground terminal of the generator base to the
ground.
The connection from the generator to the grounding must be done with twisted
copper conducting cables with a minimum section of 16mm
2
, or in case of
unavailability, galvanized iron with a section of 50mm
2
.
The ground rod will be installed during construction before the arrival of the
generator. The position, length and diameter of the earthing rod may vary
and will be determined in each case for the corresponding project, if there is
not a project, request a study to an electrical engineering to ensure that the
grounding meets all requirements to ensure safety and regulations.
WARNING
1) If the grounding terminal is unconnected by mistake or accident, it will
be very dangerous for human because leaking current inevitably goes
through the body.
2) All the bonnets of the loads must be grounded to the earth.
3) Grounding should be made before running the generator set.
Summary of Contents for 1500RPM Series
Page 2: ...1 Espa ol...
Page 13: ...12 Espa ol...
Page 34: ...33 Espa ol...
Page 35: ...34 Espa ol...
Page 45: ...44 English...
Page 47: ...46 English conductive dust lint smoke oil vapors engine exhaust fumes or other contaminants...
Page 66: ...65 English...
Page 77: ...76 Portugu s...
Page 99: ......
Page 100: ...51 POLIGONO INDUSTRIAL NEINVER CALAHORRA LA RIOJA CONTACTO INFORMA ES INFO SG GROUP ES...