4.10 Clean the dirty and dusty in the unit
Check the unit inner for dusty and dirty and clean it. Check the muffler and the
place nearthe engine for trash and flammable materials and clean them.
Check the intake andexhaust port if clogged by the dirty. Clean it, if necessary.
4.11 Electrical connection with load
Make sure that load does not exceed the power capacity of your unit. Connect
electricalconnections properly.
4.12 Checking the emergency stop button
Make sure that the emergency stop button is not pressed.
5. Operation
5.1 Start-up
1) Turn off every circuit breaker and all switches of loads.
2) Turn off the generator set main circuit breaker and other circuit breakers.
3) Press the start button on the generator set panel and the engine begins to
start. It will attempt to start about 10 seconds. If the engine fails to start, you
need to wait at least 2 minutes before retry.
4) After the engine starts successfully, allow the engine to warm up no more
than 10 minutes.
5) The control module will check the value of voltage and frequency. If the
value is abnormal, the warning LED would flash.
6) Once the generator is running at the correct voltage and frequency, turn on
the generator set main circuit breaker and the circuit breaker of loads, send
power to the load side.
WARNING
1
)
Before turning on the main circuit breaker, make sure any circuit
breaker and switch of loads are positioned to OFF. Otherwise, it may
Summary of Contents for 1500RPM Series
Page 2: ...1 Espa ol...
Page 13: ...12 Espa ol...
Page 34: ...33 Espa ol...
Page 35: ...34 Espa ol...
Page 45: ...44 English...
Page 47: ...46 English conductive dust lint smoke oil vapors engine exhaust fumes or other contaminants...
Page 66: ...65 English...
Page 77: ...76 Portugu s...
Page 99: ......
Page 100: ...51 POLIGONO INDUSTRIAL NEINVER CALAHORRA LA RIOJA CONTACTO INFORMA ES INFO SG GROUP ES...