genesis 

 

                                                                                  IG-1000 Modem - Technical Manual

 

 

Points to Note:

 

 

If the Modem fails to communicate with the panel even after the modem at the panel has 
answered then the 

time out

 setting is too short. To increase the time 

refer

 

to program-

ming option 2. 

 

 
Ensure the screen saver and power options on you PC have not been enabled. There may 
be certain conflicts between upload and downloads. 
 
Ensure the panel number is correct in the 

Set System Defaults

. Using the correct database 

is always advised. 
 
If you are still having a problem connecting to the panel via the modem, try starting a 
new database. Run the 

Auto Program

 with the correct information and upload the data 

from the panel. 
 
It is always good practice when connecting the Genesis via modem to check the COM 
Port settings and ensure that the default is set to COM Port 2. 
 
The Modem type that is recommended for remote communication to the Genesis system 
is a Netcomm Roadster Modem V.92 (pictured below), this Modem has been tested to 
operate correctly and is best suited to the Netcomm GE-1000 Modem on the panel side. 
 
 
 

NETCOMM ROADSTER 

MODEM V.92 

Page 5                                                                                                   Version 4 – May 2006 

genesis 

 

                                                                                  IG-1000 Modem - Technical Manual

 

 

OC Module Layout: 

RJ-11 PSTN line 

input jack 

DB-9 RS-323 

Serial Lead input 

Plug-in 12v DC 

input is  

Plug-on modem 

module to the 

power supply 

Power supply 

PCB base for 

modem board 

Modem Phone Line 
Input:

 

The modem phone line input is for direct connection to a 
phone line socket. This enables the modem to send and re-
ceive information for the Genesis Panel Version 2. 
  

 

 

  

DC Input:

 

The DC Input must be connected to the Genesis Version 2 
panel located at the 12v DC terminals, rather than getting its 
power from an external source. This is required so that the 
Modem Strings synchronise with the Genesis panel. 
  

DB9 Connector:

 

The DB9 Connector is a terminal, which connects directly to 
the PC RS232 Port on the Genesis Panel. This port is for 
transferring information from the Genesis through to the Mo-
dem. 

 

 

  

Modem Terminal Descriptions:

 

 

 Page  6                                                                                                Version 4 – May 2006 

genesis 

 

                                                                                  IG-1000 Modem - Technical Manual

 

 

Modem mounting:

 

 

When mounting the Modem, it is important to note the following; 
 
Optional mounting plate can be purchased 
 
Ensure the terminals do not make contact with any part of the Genesis Metal Cabinet 
(GEN-130) 
 
Avoid installing the Modem where it may be exposed to moisture, either directly (Rain, 
Sprinklers, Hoses), or by condensation. 

 
 

Settings for the Modem connected to your PC:

 

 

The Genesis Upload / Download software has been configured for use with NETCOMM 
external Modem for connection to the Genesis Panel. To set the PC Modem type for the 
Genesis: 

 

Go to the 

Technician

 tab on the Technician Software Version 3.2j or higher. 

From there you must scroll down to the 

Program

Then select the 

Dialler, Modem, STU

From this point select the 

Program Ext Modem

From here you must select the option labelled 

NETCOMM

 

Settings for the External Modem to the Genesis Panel: 

 

Genesis Technician Software V3.2j 

– Program the Modem connected to your PC by 

entering the Genesis Technicians software: 
Go to the 

Equipment Menu

 

Then scroll to 

Set System Defaults

Change the 

TIMEOUT

 to 

60

 Seconds. 

Program 

INIT 1

 as 

AT & F & D0 & K0E0S95=1

 

Program the phone number the Genesis Modem is connected to. Always program an ATD 
before the number, ensure area code is entered as well. 
Eg. Phone number (03) 9596 6688   

ATD0395966688 

 

Page 7                                                                                                   Version 4 – May 2006 

genesis 

 

                                                                                  IG-1000 Modem - Technical Manual

 

 

Initialising the Netcomm IG-1000 Modem:

 

 

The Netcomm Modem now has to talk to the Genesis Panel: 
 
Once the download is complete close the Technician Software. Remove the PC Link 
Cable and insert the Modem DB9 connection cable to the PC Link RJ45 Connection 
point. 
Power up the Modem via 12v DC auxiliary output from the Genesis Panel. 
Press and hold the RESET button on the master Panel for 1 second and release. The 
system will reset and the LED’s on the Modem will flicker indicating that the initializa-
tion string has been sent to the modem. 
 

Windows setup for Modem

 – The settings for the modem within the windows setup 

needs to be configured. Modem settings to be set: 
Go to the Modem Properties in the computer. 
Then go to the advanced settings. Here you will an open box for initialisation string. 
Now set the extra string to 

AT&F&D0&K0E0S95=1

.

 

 

 

Connecting to the Panel via the Modem: 

 

Open the Technician Software and check that the 

COM Port

 in the 

Set System De-

faults

 is set to the same port as your modem. Go 

Connect/Via Modem

. The Genesis 

modem will be called and a link established, the Comm.'s light will change from 

RED

 

to 

GREEN

Now all functions normally carried out via the PC Link can be carried out via the Mo-
dem. 

 

Connecting to Aladdin via the Modem: 

 

Open the Technician software and check that the 

COM Port

 in the 

Set System De-

faults

 is set tot he same port as your modem. 

Also ensure that the 

Modem Connection Used in Aladdin

 is selected. 

Save and exit out of the Technician software and start up Aladdin using the same data-
base as in the Technician Software. 
Log into Aladdin and then select the 

CONNECT

 Icon 

 
 