Air Handler
4
Table 3
Filters
Model No.
Filter size (inch / mm)
HNF13018/A-D
16"×20"×5/8"/406×508×15
HNF13024/A-D
16"×20"×5/8"/406×508 ×15
HNF13030/A-D
16"×20"×5/8"/406×508×15
HNF13036/A-D
19-5/16"×20-5/16"× 5/8"/490×516×15
HNF13042/A-D
19-5/16"×20-5/16"×5/8"/490×516×15
HNF13048/A-D
23"×20-5/16"× 5/8"/585×516×15
HNF13060/A-D
23"×20-5/16"×5/8"/585×516×15
Table 4
Model No.
Net Wt / Gross
Wt(kg)
Net Wt / Gross Wt
(lb)
HNF13018/A-D
52 / 56.5
114.7 / 124.6
HNF13024/A-D
53 / 57
116.9 / 125.7
HNF13030/A-D
55.5 / 59
122.4 / 130.1
HNF13036/A-D
65/ 70
143.3 / 154.4
HNF13042/A-D
67/72
147.7 / 158.8
HNF13048/A-D
79 / 84
174.2 / 185.2
HNF13060/A-D
80/86
176.4 / 189.6
Table 5
Model
Airflow
Tonnage
Range
Motor @ 230V 1Ph 60Hz
DD Blower Wheel
(inch)
Diameter-Width
SCFM vs.ESP(1)(2)
HP
FLA
0.1
0.2
0.3
0.4
0.5
HNF13018/A-D
1.5
1/16
0.62
10-8
640 590 510 430 280
HNF13024/A-D
2.0
1/5
1.52
10-8
825 748 668 519 304
HNF13030/A-D
2.5
1/4
1.25
10-8
1000 950 820 730 670
HNF13036/A-D
3.0
1/3
2.0
10-10
1150 1120 1060 990 880
HNF13042/A-D
3.5
1/3
2.0
10-10
1384 1300 1256 1205 1168
HNF13048/A-D
4.0
1/2
2.5
10-10
1510 1400 1350 1325 1265
HNF13060/A-D
5.0
3/4
4.6
11-11
1720 1650 1570 1510 1420
Notes:
①
Based upon W/nominal tonnage, dry coil and filter should be installed.
②
Use 0.96 as approximate SCFM correction factor for wet coil.