background image

Step 1: Disassemble the interlock. Place the bottom plate (holes only) above the top left breaker and mark holes.

Step 2: Turn off main breaker and remove panel cover. 

Step 3: Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover.

Step 4:   Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to screws and install 

retaining nuts. Ensure proper movement.

Step 5: Install 2 pole Generator breaker on top right side and place Generator Warning Sticker on Generator breaker.

Model

GE-200HDA MIRROR

Main Breaker

150 or 200 amp single handle Vertical throw up (on) down (off) 
Spacing between main and the first breaker is 2 

¼

 inches

Generator Breaker

Top right side 2 positions

WARNING

Only qualified personnel should be working on the panel box

An amateur should 

NEVER

 open the panel box

Please follow all rules and regulations of the National Electric Code

 

Reviews: