17
Menu
Description
Factory setting and
(max. / min values)
EE - Bypass
EE3 - Forced speed
In this menu the requested incremental forced air fanspeed can be
selected, when the bypass opens for night cooling and when the
setpoint value in EE4 is exceded.
EE4 - Forced temp.
Setpoint offset value for activation of forced air fanspeed when
bypass has opened for night cooling. (fanspeed increased by value
set in EE3) for example.
Requested temperature 20 °C
EE1 = 3 °C
Bypass opens at 23,1 °C
EE4 = 3 °C
Fanspeed increase at 26,1 °C
EE5 - Bypass time minimum on
Bypass will be open minimum according to the setpoint
EE3: 0 %
(0 - 100 %)
EE4: 3 °C
(0 - 5 °C)
EE5: 5 min
(0-60 min)
EF - Filter
EF1 - Reset filter
select this option to reset filter timer to 0 days
The current counter value will display current days since last
filterreset
EF2 - Filtertimer
Setpoint for adjusting months until filteralarm will activate
0 months = filtertimer deactived
EF3 - Filter/stop
To ensure that the filters are changed when the filter change
alarm is active, the set
point can be set to ON. The system will then stop
automatically after 14 days if the filters have not been
changed in
the meantime.
If this precaution is not required, the set point can be set to
OFF and the system will continue to operate.
EF1: reset filter
EF2: 3 months
( 0 - 12 months)
EF3: off
(On/Off)
EG - Humidity control
EG1 - Humidity max temperature
Setting the end point for outside temperaturecompensation (T3),
see the X-axis on the graph.
EG2 - Humidity max value
Setting the end point for outside temperature
compensation, see the Y-axis on the graph (desired max.
humidity value).
EG3 - Humidity fanspeed
Setting of how much the fan speed may differ in relation to
the desired fan speed.
Examples
Set point fanspeed level 2 (EB2 / EB6) = ± 15%
EG1: 15 °C
(5 - 25 °C)
EG2: 60 %
(35 - 85 %)
EG3: 15 %
(5 - 30 %)