800 523-9938
703 368-2101
Fax: 703 368-1078
E-Mail: sales@georator.com
GEORATOR Corporation
The Frequency Converter People Since 1950
9617 Center Street
Manassas, VA 20110
Model
Capacity
Input
Indicators
Protection
Output
Environment
Dimensions
Weight *
Over/Under Voltage
Overload
Output Short Circuit
Over Temperature
Voltage Regulation
Frequency (select one)
Frequency (select one)
Crest Factor
Overload Capacity
Efficiency
Humidity
Operating Temperature
Audible Noise
W x H x D (mm)
Lightning / EMC Filter
Distortion (THD)
W x H x D (in)
Kilograms
Pounds
Triathlon III UPS Specifications - 1 Phase Input to 3 Phase Output Model, 15 KVA
1 Phase 100, 110, 115, 120, 200, 208, 220, 230, or 240V ± 20%
15 KVA
T3UPS-13-15K
50 or 60 Hz ± 5% (Optional 400Hz)
3 Phase Delta 220/380/460V (+/-5% adjustable)3 Phase Wye
190/200/208/220/230/240V (+/-5% adjustable)3 Phase Wye
380/400/415/440/460/480V (+/-5% adjustable)
± 1% at Linear Load
50 or 60Hz ±0.1 Hz (Optional 400 Hz)
< 2.0% (Linear Load)
3:1
125% for 15 Minutes, 150% for 10 Minutes, > 150% for 1 Minute
>= 93%
Power Walk In
0-100%: 20 seconds
EMI/EMC
Power Factor
0.8
< 0.5 Deg.
LCD
LED
Real Time Status, Data or Historical Events, Parameters, Real Time Clock, Inverter
& Alarm
Up to date information (Status) to the User & Audible Alarm
Alarm
Auto-shutdown
Auto-shutdown 25 sec. later
Auto-shutdown
Surge and Lightning Protection
EN50091-2 Approved
0° – 40° C
0 - 90% Non-condensing
< 65 dB at 1 meter
550*1,600*800
21.7*63.0*31.5
380.0
837.8
Phase Shift (unbal. load)
Contact Closure, RS-232/485
Supports MEGATEC RUP, MEGATEC RUPSII, UPSilon 2000 UPS monitoring software
Interface
Battery
Type - Quantity
Backup Time **
Minutes - Minimum
HR1234W - 58 ea.
15 min.
Battery
Kilograms
Pounds
85.0
188.5
Weight
Voltage
(select one individual voltage)
Voltage
(select one individual voltage)
Galvanic Isolation
Input & Output True Galvanic Isolation
Standards
FCC Class A
EN50091-1, -2
YES
YES
* Weights based on 220/380V IN and OUT. Weights may vary based on input/output frequency/voltage
** Longer backup times (to 8 hours) are available from standard models; custom specifications also available.
Summary of Contents for Triathlon III T3UPS-13-15K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Page 24: ...INTER PCB DIAGRAM 1 19...
Page 31: ...1...
Page 35: ...3 3...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Page 80: ...3...
Page 81: ......