3.3. Cable Selection
The following tables list typical information concerning the KVA of the UPS versus
the size and rating of the cables. Inadequate cable size or over sized breakers will
incur risk of fire or damage of insulation. Therefore, please use the following tables to
determine the input circuit breaker rating and the size of cable for input, output and
battery connections. These data are for reference; final decisions should be made in
accordance with the local electrical codes.
BREAKER RATING FOR INPUT
KVA
INPUT
Imax(A)
NFB(A)
20 277/480V
3
Φ
42 50
30 277/480V
3
Φ
60 60
40 277/480V
3
Φ
82 100
50 277/480V
3
Φ
100 100
60 277/480V
3
Φ
123 125
80 277/480V
3
Φ
143 150
100 277/480V
3
Φ
175 175
120 277/480V
3
Φ
215 225
160 277/480V
3
Φ
286 300
240 277/480V
3
Φ
400 400
320 277/480V
3
Φ
583 600
3-6