CABLE SIZE FOR INPUT
KVA INPUT In(A)
R/S/T(mm
2
) N(mm
2
)
20 277/480V
3
Φ
30 8 14
30 277/480V
3
Φ
45 8 14
40 277/480V
3
Φ
60 14 22
50 277/480V
3
Φ
75 22 38
60 277/480V
3
Φ
90 22 38
80 277/480V
3
Φ
120 38 60
100 277/480V
3
Φ
150 60 80
120 277/480V
3
Φ
180 80 100
160 277/480V
3
Φ
240 100 125
240 277/480V
3
Φ
346 60*2 80*2
320 277/480V
3
Φ
461 100*2 125*2
3-7
Summary of Contents for Triathlon III T3UPS-13-15K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Page 24: ...INTER PCB DIAGRAM 1 19...
Page 31: ...1...
Page 35: ...3 3...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Page 80: ...3...
Page 81: ......