5-4
The inverter should be shut off under a short circuit condition. Since the CPU will
detect a short circuit, and in order to avoid unnecessary tripping and damage to the
breaker, the static switch remains connected to the inverter (will not transfer to
reserve).
Listed below are all the warning conditions that can be displayed (arranged in order
of priority, starting with the highest priority):
1st row : BYPASS ON / RECT AC FAIL / RECTIFIER PHASE ERROR /
RESERVE FREQ. ERROR
2nd row : 170% OVERLOAD / 150% OVERLOAD / 125% OVERLOAD /
110% OVERLOAD
3rd row : BATTERY LOW STOP / BATTERY LOW / BATTERY BAD /
BATTERY GND FAULT / BATTERY TESTING
Lists below are all the fault conditions that can be displayed:
1st row : HIGH DC SHUTDOWN
2nd row: SHORT CIRCUIT! / FUSE/OVERHEAT / OVERLOAD
SHUTDOWN / EMERGENCY STOP / INVERTER ABNORMAL
3rd row : BYPASS ON SHUTDOWN
The UP (
↑
) or DOWN (
↓
) key has no function in this menu. The screen will go
back to MENU 1 – the SELECT menu, when ENTER (
←┘
) is pressed.
5.4. Menu 3 – Real Time Data Menu
<
R E A L
T I M E
D A T A
>
→
R E C T I F I E R
D A T A
O T H E R
D A T A
R E S E R V E
D A T A
O U T P U T D A T A
E X I T
Summary of Contents for Triathlon III T3UPS-13-15K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Page 24: ...INTER PCB DIAGRAM 1 19...
Page 31: ...1...
Page 35: ...3 3...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Page 80: ...3...
Page 81: ......