Maintenance Bypass Mode:
In case of UPS maintenance or battery replacement, and where the load cannot be
interrupted, the user can turn off the inverter, close the bypass breaker and then open
the rectifier and reserve breakers. The AC output will not be interrupted during
manual bypass transfer procedure. Therefore, the maintenance bypass switch keeps
continuously supplying power to the load. Electricity will not exist in UPS except the
output transformer, thus ensuring the safety of service personnel.
Generally, the UPS is expected to run 24 Hours a day in normal operation mode once
it is installed, except when the utility power fails, under overload conditions, or
during maintenance.
Normal operation with batteries connected provides clean, stable, regulated and
uninterrupted power to the load, free from any spikes and surges. Therefore, the UPS
can be regarded as a perfect AC power source, limited in back-up time, under mains
failure, only by the capacity of the batteries.
1-4
Summary of Contents for Triathlon III T3UPS-13-15K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18...
Page 24: ...INTER PCB DIAGRAM 1 19...
Page 31: ...1...
Page 35: ...3 3...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM...
Page 80: ...3...
Page 81: ......