70

7. Setting Up the Actuator

Attention

Check the following before connecting the actuator
to the mains:
ł Does the mains voltage correspond to the speci-

fications given on the typeplate

ł Has the actuator been connected correctly

(see Section 5.1)

Adjustments

If a complete valve is supplied by Georg Fischer,
no further adjustments are required.
After installation by the customer or after repair
work, the end positions should be checked and if
necessary adjusted.

Limit switch allocation

Switch S1 (bottom) opens at «open» position
Switch S2 (top) opens at «closed» position

Procedure

Set both switching cams (1) to S1* and S2* so that
the rotating angle is less than 90°.
Let the actuator turn until a limit switch is activated.
By adjusting the respective switching cam, the end
position can be set since the actuator follows the
cam.

* S1: «open», bottom

S2: «closed», top

!

Summary of Contents for EA 11

Page 1: ...Bedienungsanleitung Instruction de service Instruction Manual Elektrischer Stellantrieb Typ EA 1 Servom canisme lectrique Type EA 1 Electrical Actuator Unit Type EA 1 Piping Systems...

Page 2: ...technischen Daten sind unverbindlich Sie gelten nicht als zugesicherte Eigenschaften oder als Beschaffenheits oder Haltbarkeitsgarantien nderungen vorbehalten Es gelten unsere Allgemeinen Verkaufsbedi...

Page 3: ...r Gesamtarmatur 10 6 1 Montage Kugelhahn Typ 07 6 2 Aufbau bersicht Kugelhahnsystem Typ 07 7 Inbetriebnahme des Antriebes Armatur 14 7 1 Handnotbet tigung 8 Technische Daten Stellantrieb EA 1 16 9 Mon...

Page 4: ...drohende Gefahr Bei Nichtbeachtung drohen Ihnen Tod oder schwerste Verletzungen M glicherweise drohende Gefahr Bei Nichtbeachtung drohen Ihnen schwere Verletzungen Gef hrliche Situation Bei Nichtbeach...

Page 5: ...u bestimmt nach Aufbau auf eine Armatur und Anschluss an eine anlagenseitig beigestellte Steuerung Armaturen mit 90 Schwenkbewegung Kugelh hne und Klappen zu bet tigen die vorher einjustierten Endstel...

Page 6: ...3 beschrieben ist er die Bedienungsanleitung und die Anleitung der zugeh rigen Armatur kennt und die darin enthaltenen Hinweise beachtet und Vorkehrungen gegen elektrostatische Einwirkun gen getroffen...

Page 7: ...rpackung transportiert und oder gelagert werden Die Antriebe sind vor sch dlichen physikalischen Einfl ssen wie Staub W rme Feuchtigkeit zu sch tzen Insbesondere die Anschl sse d rfen weder durch mech...

Page 8: ...kann der Antrieb zu s tzlich mit verschiedenen Erg nzungsbaus tzen ausger stet werden siehe Punkt 9 1 Endschalter S1 und S2 2 Gleichstrommotor 3 Optische Stellungsanzeige 4 Stecker f r Zubeh r 5 Ansc...

Page 9: ...lieren Erdleiter nicht schalten Querschnitt der Zuleitungen max 5 mm2 Um ein Eindringen von Wasser in den Antrieb zu vermeiden darf die Kabeleinf hrung nicht nach oben zeigen 5 1 Anschlussschema Stand...

Page 10: ...rk voreingestellt Es ist not wendig nach einer kundenseitigen Montage eine Nachjustierung vorzunehmen siehe Punkt 7 Vorgehen bei der Montage siehe Bild 6 1 Die Adapterplatte mit den bereits fixierten...

Page 11: ...Sie dabei auf die eckige a bzw runde b Kontur sowie die Position der asymmetrischen Aus sparung c des Zapfens Ziehen Sie die 4 vormontierten Schrauben Torx an Das MF Modul ist nun fest mit dem Kugelha...

Page 12: ...12 6 1 Kugelhahn Typ 07 Stellantrieb Typ EA 1 Kupplungsst ck Adapterplatte PT Schr KA 4x 6 Klammer Innensechskantschrauben Kupplung Schrauben Multifunktions Modul ohne Mikroschalter Kugelhahn Typ 546...

Page 13: ...4 Hinweis Schraubensicherung Die Schrauben zur Befestigung des Antriebes werden mit Loctite 243 oder quivalentem Klebstoff gesichert Hinweis Montage Kupplung mit Kupplungsst ck Zuerst muss das Kupplu...

Page 14: ...hr notwendig Bei kundenseitiger Montage oder nach einer Reparatur sind die Endlagen zu kontrollieren und bei Bedarf nachzujustieren Endschalterzuordnung Schalter S1 unten ffnet bei Auf Position Schalt...

Page 15: ...ffnung einstecken siehe Bild Seite 8 Nr 7 Funktion Handkurbel bis zum Anschlag niederdr cken Mit neun Umdrehungen wird die Kugel um 90 gedreht Drehrichtung Uhrzeigersinn CW schliessen Gegenuhrzeigers...

Page 16: ...90 Nenndrehmoment 10 Nm Spitzendrehmoment 20 Nm Umgebungstemperatur 10 bis 45 C 2 Zul ssige Luftfeuchtigkeit max 80 bis 31 C 4 Verschmutzungsgrad 5 2 berspannungskategorie 5 II Geh usewerkstoff PP gl...

Page 17: ...ent wird auf die Basisplatine aufmon tiert und ist ber ein Flachkabel X1 mit dieser elek trisch verbunden Mit einem Temperatursensor der auf diesem Element montiert ist wird die Tempera tur gemessen u...

Page 18: ...18 Heizelement Bausatz LED leuchtet Normalbetrieb LED leuchtet Heizbetrieb...

Page 19: ...direkt ber hren Elektrostatische Entladungen k nnen Bauteile besch digen Die drei Distanzbolzen 1 in die Montagebolzen einschrauben Handfest anziehen Platine 3 mittels mitgelieferten Schrauben 2 auf d...

Page 20: ...matisch den Akku zu Mit dem Tippschalter kann die Funktion Anfahren der ZU Stellung oder Anfahren der AUF Stellung gew hlt werden Stellung 2 ZU Position Stellung ON AUF Position immer beide Schalter s...

Page 21: ...21 R ckstelleinheit Bausatz LED leuchtet Normalbetrieb LED leuchtet Akkubetrieb...

Page 22: ...nen Bauteile besch digen Die drei Distanzbolzen 1 in die Montage bolzen einschrauben Handfest anziehen Platine 3 mittels der Schrauben 2 auf dem Distanzbolzen befestigen Flachkabel in die Stecker X1 e...

Page 23: ...ten Code Bausatz 2 zus tzliche 250 V p 6 A 199 190 092 Endschalter Ag Ni Wird der Endschalterbausatz im Werk montiert sind die Schalter als ffner verdrahtet gem ss Schema Eine Umstellung auf Schliesse...

Page 24: ...24 Endschalter Bausatz...

Page 25: ...stellen der Endschalterposition Ger t wieder an die Versorgungsspannung an schliessen Mittels Schraubenzieher Gr sse 2 k nnen die Schaltnocken verstellt werden Die Einstellung der Schaltposition darf...

Page 26: ...einer Behinderung der W rmeausdehnung L ngs bzw Biegekr fte auf Um die Funktionsweise der Armatur nicht zu be eintr chtigen m ssen diese Kr fte durch geeignete Festpunkte vor bzw hinter der Armatur au...

Page 27: ...uft nur noch Umschaltrelais Basisplatine aus in einer Drehrichtung funktioniert nicht tauschen berlastschutz spricht Reibdrehmoment an Armatur reinigen und an wieder ein der Armatur zu hoch schmieren...

Page 28: ...l Akku 199 190 087 Akkubausatz 198 151 317 Steckersatz 198 000 502 Handnotschl ssel 198 151 307 Handnotdeckelsatz Verschlussschraube 198 000 503 Multifunktions Modul ohne Endschalter leer Dimensionen...

Page 29: ...Instruction de service Servom canisme lectrique Type EA 1...

Page 30: ...30 Les donn es techniques s entendent sans engagement Elles ne repr sentent pas des propri t s garanties et sont sujettes des modifications Veuillez consulter nos Conditions G n rales de Vente...

Page 31: ...rd 6 Montage de l ensemble de la robinetterie 38 6 1 Robinet bille type 107 6 2 Vue d ensemble de la construction du syst me de robinet bille type 107 7 Mise en service du servom canisme de la 42 robi...

Page 32: ...as de non respect des accidents mortels ou graves vous menacent Danger possible En cas de non respect de graves blessures vous menacent Situation dangereuse En cas de non respect de l g res blessures...

Page 33: ...elon les dispositions Apr s montage sur un robinet et raccordement une commande pr vue sur l installation le pr sent servom canisme est destin actionner des robinets pivotants 90 robinets bille et cla...

Page 34: ...service et des directives des robinets corre spondants et observe les avertissements qui en font partie des mesures de pr vention contre les effets lectrostatiques ont t prises 4 2 Types de dangers p...

Page 35: ...iginal non ouvert les servom canismes sont prot ger des influ ences physiques nuisibles telles que poussi re chaleur humidit les raccordements en particulier ne doivent pas tre endommag s par des infl...

Page 36: ...eut tre galement quip de diff rentes options suppl mentaires voir point 9 1 Interrupteurs de fin de course S1 et S2 2 Moteur courant continu 3 Indication optique de position 4 Fiche pour accessoires 5...

Page 37: ...commuter le c ble de masse La section maximale du connecteur est de 5 mm2 Pour viter l entr e de l eau dans le servom canisme l entr e du c ble ne doit pas pointer vers le haut 5 1 Sch ma de raccorde...

Page 38: ...canisme ont t pr r gl es en usine Apr s le montage par le client un r ajustage est n cessaire voir point 7 Comment proc der au montage voir illustration 6 1 Bien visser la plaque d adaptation au serv...

Page 39: ...arr s a ou ronds b ainsi que la position de la rainure asym trique c du pivot Serrez les 4 vis pr mont es Torx A pr sent le module MF est bien fix au robinet bille Placer l accouplement et la pi ce d...

Page 40: ...net bille type 07 Servom canisme de type EA 1 Pi ce d accouplement Plaque d adaptation PT Schr KA 4x 6 Pince Vis six pans creux Accouplement Vis Module multifonction sans microinterrupteur Robinet bil...

Page 41: ...5 2 3 4 3 4 3 DN 40 5 4 Note Consolidation de vis Les vis de fixation pour le servom canisme sont assur s avec Locitite 243 ou similaire Note Montage d accouplement avec pi ce d accouplement Mettre d...

Page 42: ...par le client ou apr s r paration les fins de course sont contr ler et le cas ch ant r ajuster Attribution des interrupteurs de fin de course L interrupteur S1 en bas ouvre en position ouverte L inte...

Page 43: ...l ouverture voir illustration 34 n 7 Fonction Enfoncer la manivelle main jusqu la but e Tourner la bille d un de 90 en effectuant neuf rotations Sens de la rotation Sens horaire CW fermer Sens anti h...

Page 44: ...en pointe 20 Nm Temp rature ambiante de 10 45 C 2 Humidit ambiante admissible max 80 jusqu 31 C 4 Degr e de pollution 5 2 Cat gorie de surtension 5 II Mati re du bo tier PP renforc de fibre de verre...

Page 45: ...accordement L l ment chauffant est mont sur la platine de base et est reli lectriquement celle ci par un c ble plat X1 Gr ce un d tecteur de temp ra ture mont sur cet l ment la temp rature est mesur e...

Page 46: ...46 Jeu de montage l ment chauffant LED luire Service normale LED luire Chauffage en service...

Page 47: ...cher directement la platine Des d charges lectrostatiques pourraient endommager certains l ments Serrer les trois boulons d cartement 1 dans les boulons de montage Serrer la main Fixer la platine 3 su...

Page 48: ...apr s 5 sec La fonction Aller en posi tion FERMEE ou aller en position OUVERTE peut tre s lectionn e au moyen d une touche impul sion Position 2 FERMEE position ON OUVERTE voir l image gauche L accu...

Page 49: ...49 Jeu de montage r tropositionneur LED luire Service normale LED luire Accu en service...

Page 50: ...statiques pourraient endommager certains l ments Serrer les trois boulons d cartement 1 dans les boulons de montage Serrer la main Fixer la platine 3 sur le boulon d cartement l aide des vis 2 Introdu...

Page 51: ...199 190 092 2 Interrupteurs de fin de course suppl men taires Ag Ni Lorsque le jeu de montage de l interrupteur de fin de course est mont l usine les interrupteurs sont c bl s comme contacts d ouvertu...

Page 52: ...52 Jeu de montage 2 interrupteurs de fin de course...

Page 53: ...ge de la position de fin de course Rebrancher l appareil sur la tension d alimentation Les cames peuvent tre r gl es l aide d un tourne vis de dimension 2 Le r glage de la position d enclenchement ne...

Page 54: ...produisent dans les syst mes de tuyauterie soumis des fluctuations de temp rature Afin de ne pas compromettre le fonctionnement de la robinetterie les forces doivent tre absorb es par des points fixe...

Page 55: ...ommutateur Remplacer la platine que dans une direction ne fonctionne pas de base Protection en cas de Moment de couple Nettoyer et graisser surcharge activ e trop haut sur robinet la robinetterie r al...

Page 56: ...onneur avec accu 199 190 087 Jeu de montage accu 198 151 317 Connecteur complet 198 000 502 Manivelle main 198 151 307 Vis de fermeture 198 000 503 Module multifonction sans interrupteur de fin de cou...

Page 57: ...Instruction Manual Electrical Actuator Unit Type EA 1...

Page 58: ...58 The technical data is not binding and not an expressly warranted characteristic of the goods It is subject to change Please consult our General Conditions of Supply...

Page 59: ...5 1 Wiring Diagram for Standard Version 6 Valve Design 66 6 1 Mounting on the Ball Valve 07 6 2 Overview of Ball Valve System Type 07 7 Setting Up the Actuator Valve 70 7 1 Emergency Manual Override 8...

Page 60: ...nt acute danger Failure to comply could result in death or extremely serious injury Possible acute danger Failure to comply could result in serious injury Dangerous situation Failure to comply could l...

Page 61: ...unted on a valve and connected to a system control the purpose of this actuator is to actuate valves with 90 pivoting ball valves and butterfly valves indicate the previously calibrated end positions...

Page 62: ...truction manual and the manual of the corresponding valve and adheres to the instructions contained therein and he has taken the necessary measures against electrostatic influence 4 2 Special hazards...

Page 63: ...nd or stored in their original unopened packaging The actuators must be protected from harmful physical influences such as dust heat humidity It is important that the connections are neither damaged b...

Page 64: ...he actuator can be equipped additionally with various supplementary kits see Section 9 1 Limit switches S1 and S2 2 Direct current motor 3 Optical position indicator 4 Plug for accessories 5 Terminal...

Page 65: ...or between the actuator and the power supply do not disconnect the earthcable To avoid water flowing into the actuator it is necessary that the cable insertion ist not upturned 5 1 Wiring Diagram for...

Page 66: ...e been preset in the factory It is necessary to readjust these after installation at the customer see Section 7 How to assemble see Fig 6 1 Screw the adapter plate with the fixed clamps tightly onto t...

Page 67: ...a and round b contours as well as the position of the asymmetrical recesses c of the stem Tighten the 4 pre assembled screws Torx The MF module is now firmly connected with the ball valve Insert the c...

Page 68: ...68 6 1 Ball Valve Type 07 Actuator Type EA 1 Coupling piece Adapter plate PT Schr KA 4x 6 Clamp Allen screws Coupling Screws Multifunctional module without microswitches Ball valve type 546...

Page 69: ...2 5 DN50 5 2 3 4 3 4 3 DN 40 5 4 Note Screw saving The actuator fixing screws are assured with Locitite 243 or equivalent Note Mounting of coupling and coupling piece First plug the coupling piece int...

Page 70: ...ents are required After installation by the customer or after repair work the end positions should be checked and if necessary adjusted Limit switch allocation Switch S1 bottom opens at open position...

Page 71: ...on shaft under the opening see illustration page 60 no 7 Function Push the crank down to the stop With nine revolutions the ball is rotated by 90 Direction of rotation Clockwise CW close Counterclockw...

Page 72: ...inal torque 10 Nm Peak torque 20 Nm Ambient temperature 10 to 45 C 2 Allowable humidity max 80 up to 31 C 4 Pollutiongrade 5 2 Overvoltage category 5 II Housing materials PP fiberglass reinforced flam...

Page 73: ...heating element is mounted on the base board and is connected electrically via a flat cable X1 The temperature is measured with a temperature sensor which is mounted on this element and between appro...

Page 74: ...74 Heating element kit LED shines normal operation LED shines heating operation...

Page 75: ...Do not touch the board itself Electrostatic discharge can damage the components Screw the three distance bolts 1 into the assembly bolts Screw hand tight Fasten the board 3 to the distance bolts with...

Page 76: ...age battery automatically after 5 sec With a touch control the function Go to the CLOSED or OPEN position can be selected Position 2 CLOSED position ON OPEN always both see at left The storage battery...

Page 77: ...77 Fail safe return kit LED shines normal operation LED shines accu operation...

Page 78: ...components Screw the three distance bolts 1 into the assembly bolts Screw hand tight Fasten the board 3 to the distance bolts with the screws 2 Plug the flat cable into the X1 connector Reconnect to...

Page 79: ...ta Code Kit with 2 additional 250 V p 6 A 199 190 092 limit switches Ag Ni If the limit switch kit is mounted in the factory the switches are wired as opener according to the diagram It is possible fo...

Page 80: ...80 Limit switches kit...

Page 81: ...ll as the spacer rings Setting the limit switch position Reconnect to the supply voltage The switching cams can be adjusted with a screw driver size 2 An instrument e g ohm meter must be used for sett...

Page 82: ...inal or bending forces occur if thermal expansion is hindered So as not to impair valve functioning these forces must be absorbed by the appropriate fixed points in front of or behind the valve The fa...

Page 83: ...lve replace motor Motor only runs in Change over relay Replace base one direction does not work board Overload protection Friction torque of Clean and lubricate reacts self re valve too high valve set...

Page 84: ...t fail safe return with battery 199 190 087 Battery kit 198 151 317 Plug complete 198 000 502 Crank 198 151 307 Cover Screw kit 198 000 503 Multifunctional module without limit switches empty Dimensio...

Page 85: ...85 Notes...

Page 86: ...86...

Page 87: ...87...

Page 88: ...4 0 2476 530 450 info georgefischer co uk www georgefischer co uk GR Georg Fischer S p A Athens Branch 101 3rd September Str 10434 Athen Tel 30 0 1 882 0491 Fax 30 0 1 881 0291 info piping georgfische...

Reviews: