User Manual - P series
14
www.georgin.com
4. Type A adjustment : fixed dead band instrument
VG:
RG:
IG:
ES:
LP:
C:
Range adjustment screw
Range spring
Range index
Sensing element
Flexible arm
Switch
4.1. Procedure A1: Single instrument
Example: 6-bar rising setting
4.1.1. Adjusting the set point
1. Raise the pressure to the threshold (6 bar) and stabilise it.
2. Using set point adjustment screw VG, relax range spring RG until switch(es) C changes state.
4.1.2. Checking/Adjusting the set point
3. Slowly raise the pressure, and then slowly lower it again. Measure the lower and upper triggering thresholds.
4. Fine-tune the settings using adjustment screw VG (Lower and Upper threshold control).
5. Disconnect the instrument from the bench.
6. Apply a seal to adjustment screw VG using a Georgin seal kit (torque: 1.7 N∙m ±10%).
7. Close the cover and tighten the two captive screws (torque: 1.2 N∙m).