background image

9

General Installation Information cont.

Air Handler Installation

The air handler is attached to the shipping pallet with screws. Prior 
to setting the unit in place remove the shipping screws located in 
the front base right behind the air filter access panel. Also remove 
the external shipping brackets at the rear of the cabinet.

An air filter must always be installed upstream of the air coil on the 
return air side of the air handler.  An air filter is provided with the 
air handler.  If there is limited access to the filter rack for normal 
maintenance, it is suggested that a return air filter grille be installed.  
In this instance the filter supplied with the air handler should be 
removed.  Be sure that the return duct is properly installed and free 
of leaks to prevent dirt and debris from bypassing the filter and 
plugging the air coil.

The cabinet should be sealed so that unconditioned warm air can 
not enter the cabinet.  Warm air will introduce moisture into the 
cabinet which could result in water blow-off problems, especially 
when installed in an unconditioned space.  Make sure that the 
liquid line, suction line and drain line entry points into the cabinet 
are well sealed. Use the butyl tape supplied with the air handler to 
seal around the copper lines entering the cabinet.

All wall penetrations should be sealed properly. The line set should 
not come into direct contact with water pipes, floor joists, wall 
studs, duct work, floors, walls and brick. The line set should not 
be suspended from joists or studs with a rigid wire or strap which 
comes into direct contact with the tubing. Wide hanger straps which 
conform to the shape of the tubing are recommended.  All line sets 
should be insulated with a minimum of 3/8” closed cell insulation.  
The line set insulation should be pliable, and should completely 
surround the refrigerant line.  As in all R-410a equipment, a 
reversible liquid line filter drier is required to insure all moisture 
is removed from the system. This drier is factory installed in the 
series compressor section. This drier should be replaced whenever 
“breaking into” the system for service. All exterior insulation should 
be painted with UV resistant paint or covering to insure long 
insulation life.

Connection to the Coil

Connect the refrigerant line set to the ‘A’ coil tubes.  Nitrogen 
should be bled through the system at 2 to 3 PSI to prevent 
oxidation inside the refrigerant tubing.  Use a low silver phos-
copper braze alloy on all brazed connections.  The air handler 
TXV bulb is secured to the ‘A’ coil for shipping.  The indoor and 
outdoor compressor section is shipped with a factory charge and 
the service valves are not to be opened until the line set and air 
handler have been leak tested, purged and evacuated.  A damp 
towel or heat sink should be used on the service valves to prevent 
damage caused by excessive heat.

Refer to the Refrigerant Line Sizing table to determine the proper 
line set configuration for the system being installed.  Line sets over 
60 feet in length are not recommended.  If the line set is kinked or 
deformed and cannot be reformed, the bad section of pipe should 

be replaced.  A restricted line set will affect unit performance.  
Line sets should be routed as directly as possible, avoiding any 
unnecessary bends and turns.

Important Note:
The bulb will need to be attached to the suction line on the outside of 
the cabinet once the refrigerant line connections have been made.

Leak Testing

The refrigeration line set must be pressurized and checked for 
leaks before purging and charging the unit.  To pressurize the line 
set, attach refrigerant gauges to the service ports and add an inert 
gas (nitrogen or dry carbon dioxide) until pressure reaches 60 to 90 
PSIG.  Never use oxygen or acetylene to pressure test the system.  
Use an electronic leak detector or a good quality bubble solution to 
detect leaks on all connections made in the field.  Be sure to check 
the service valve ports and stems for leaks.  If a leak is found, 
repair it and repeat the above steps.  For safety reasons do not 
pressurize the system above 150 PSIG.  Purge pressure from the 
line set slowly when the pressure test is complete.  The system is 
now ready for evacuation.

System Evacuation

Ensure that the line set and air coil are evacuated before opening 
service valves.  The line set and air coil must be evacuated to 
250 microns with a good quality vacuum pump and use a vacuum 
gauge to ensure that air and moisture are removed.  With the 
system shut off from the vacuum pump a sufficient system vacuum 
is achieved when a 500 micron vacuum can be held for 30 minutes.  
A fast rise to atmospheric pressure indicates a leak, while a slower 
rise to around 1500 microns indicates moisture is still present in the 
system and further evacuation is required.

Refrigeration

The GAH series air handlers are supplied with an expansion 
device. Once the line set has been brazed into the air handler 
the txv bulb must be attached to the suction line outside of the 
cabinet and insulated with foam tape. Be careful not to crush the 
txv bulb by over-tightening the clamp.  The txv supplied has an 
internal check valve so no external check valve is necessary.  The 

ASTON SERIES AIR HANDLER INSTALLATION MANUAL

Summary of Contents for GAH022

Page 1: ...I N S TA L L AT I O N M A N U A L GEOTHERMAL HEAT PUMPS AFF ORDABLE RENEWABLE CLEAN A S T O N S E R I E S A I R H A N D L E R...

Page 2: ......

Page 3: ...tallation Information 5 11 Hydronic Models 12 13 Electrical Data 14 15 Wiring Schematics 16 18 ECM Blower Control 19 Blower Performance Data 20 Dimensional Data 21 24 Unit Startup 25 Replacement Proce...

Page 4: ...1 3 4 6 7 8 9 10 11 12 Model GAH G Series Air Handler Unit Capacity Refrigeration DX Models with Nominal CFM 022 MBTUH 800 026 MBTUH 925 030 MBTUH 980 036 MBTUH 1225 042 MBTUH 1425 048 MBTUH 1625 060...

Page 5: ...H026 GAH030 GAH036 GAH042 GAH048 GAH060 Air Coil Total Face Area ft2 m2 Tube outside diameter in mm Number of rows Fins per inch Suction line connection in mm sweat Liquid line connection in mm sweat...

Page 6: ...glass or constructed of ductboard for the first few feet On systems employing a metal duct system canvas connectors should be used between the unit and the ductwork If air noise or excessive airflow i...

Page 7: ...eeze It is recommended that the trap material be of a type that will allow for expansion of water when it freezes Drain lines must be in conformance with local codes Air Handler Configuration The air...

Page 8: ...installed on combustible flooring protect the edges of the floor opening with sheet metal over wrap or other non combustible material 9 Bottom air discharge units should be sealed well to the floor to...

Page 9: ...is secured to the A coil for shipping The indoor and outdoor compressor section is shipped with a factory charge and the service valves are not to be opened until the line set and air handler have be...

Page 10: ...actory set 33P609 03 factory set 33P609 05 factory set open 2 turns 33P609 06 open 2 turns Note When installing these air handlers follow the table for initial txv setting Check sub cooling and superh...

Page 11: ...11 General Installation Information cont Figure 4 Decrease Superheat Open Valve Increase Superheat Close Valve ASTON SERIES AIR HANDLER INSTALLATION MANUAL...

Page 12: ...n tank to allow room for the heated liquid to expand A system is considered closed when a check valve or backflow prevention valve is installed in the cold water pipe upstream of the water heater Once...

Page 13: ...6 0 1 4 1 4 1 4 1 2 1 2 1 2 1 2 9 0 2 8 2 6 2 5 2 4 2 4 2 4 2 3 12 0 4 6 4 4 4 2 4 0 4 0 4 0 3 9 15 0 7 0 6 8 6 6 6 0 6 0 5 9 5 8 Water Presure Drop Hydronic Coil Entering Water Temperature F EAT F 10...

Page 14: ...of Circuit Breaker One and on the L2 side of Circuit Breaker Two The voltmeter should read approximately 0 volts If the meter reads high voltage the aux iliary heat breakers need to be rewired so that...

Page 15: ...765 single 900 4 0 34 7 40 0 38 7 44 0 48 4 55 0 50 60 042 0 0 7 0 7 0 7 0 8 8 8 8 15 15 9 6 32 765 single 900 7 0 34 7 40 0 41 7 47 0 52 1 58 8 60 60 14 4 49 147 single 1 275 7 0 52 0 60 0 59 0 67 0...

Page 16: ...iring Optional block DC Voltage PCB traces Internal junction Quick connect terminal Thermal Limit Switch Field wire lug Ground HE PB SW1 Heater element Power block DIP package 10 position Legend N O N...

Page 17: ...Gry 6 Yel 15 Yel 7 P2 P1 C 1 2 3 4 Gray ER4 NO ER3 NO ER2 NO ER1 NO C 1 2 3 4 HE3 TS3 NOTE 2 Grn 9 Air Handler 5kW Electric Heat Thermostat R C Y1 O W Y2 Transformer G Grn 2 3 4 5 1 Blk Wh Yel 24V 20...

Page 18: ...Yel 22 P2 Gray ER4 NO NOTE 2 ER3 NO ER2 NO ER1 NO C 1 2 3 4 C 1 2 3 4 P1 PNK 19 Pnk 23 Pnk 27 HE4 TS4 Pnk 18 Air Handler w 15kW Electric Heat Thermostat R C Y1 O W Y2 Transformer G Grn 2 3 4 5 1 Blk W...

Page 19: ...r field selection of humidity control via setting DIP 9 off The cooling airflow settings are determined by the Cooling Heating DIP switch settings above Dehumidification mode reduces the selected norm...

Page 20: ...0 580 440 On Off 975 0 50 1 2 Off Off 800 630 425 Off Off 900 036 0 50 1 2 On On 1300 1025 760 Off 1105 871 760 On On 1300 0 50 1 2 Off On 1225 950 685 Off 1041 808 685 Off On 1250 0 50 1 2 On Off 115...

Page 21: ...2 0 3 9 26 7 39 4 Condensate is stainless steel 3 4 O D tube Discharge flange is field installed and extends 1 25 4 mm from cabinet 026 060 Refrigerant Water Connections GG HH II S T U V W X Y Z AA B...

Page 22: ...ondensate is stainless steel 3 4 O D tube Rev 4 28 14 Discharge flange is field installed and extends 1 25 4 mm from cabinet Refrigerant Water Connections 026 060 CC DD EE S T U V W X Y Z AA BB 1 cond...

Page 23: ...2 7 9 2 0 3 9 26 7 39 4 Condensate is stainless steel 3 4 O D Discharge flange is field installed and extends 1 25 4 mm from cabinet 026 060 Refrigerant Water Connections GG HH II S T U V W X Y Z AA B...

Page 24: ...2 4 Condensate is stainless steel 3 4 O D Rev 8 15 14 Discharge flange is field installed and extends 1 25 4 mm from cabinet Refrigerant Water Connections 026 060 CC DD EE S T U V W X Y Z AA BB 1 cond...

Page 25: ...coil should be cleaned before startup A 10 percent solution of dishwasher detergent and water is recommended for both sides of coil A thorough water rinse should follow Maintenance Filters Filters mus...

Page 26: ...ronic Models 022 R 026 R 030 R 036 R 042 R 048 R 060 R 026 H 036 H 048 H 060 H Refrigeration Air Coil 61S641 02 61S640 02 61S642 02 TXV 33P609 01 33P609 03 33P609 05 33P609 06 N A ECM Motor Blower Blo...

Page 27: ...t Up 01 April 2015 MA 5 7 22 24 Updated Hydronic Data 15 Aug 2014 MA 4 6 19 20 Updated Drain Pan 20 May 2014 DS MA All Updated Dimensional Data for New Vertical Condensate Drain 02 May 2014 DS All Upd...

Page 28: ......

Page 29: ......

Page 30: ...R 410A Size 2 5 Tons Document Type Installation Manual Part Number IM1008HG Release Date 07 15 2015 The manufacturer has a policy of continual product research and development and reserves the right t...

Reviews: