(863) 248-2800
www.sensocon.com
3
Installation and Operation
Manual
Series A3 & A4
The Sensocon A3 and A4 series of differential pressure controllers provide control
of low differential pressure applications for air and other compatible non
combustible gasses. These instruments have a large LED display for pressure
indication, a LCD or OLED display for programming and additional LED’s to
indicate % of output, setpoints and alarm status. The instruments are fully
programmable from the key pad face or by utilizing the Opti-Link™
communication port for no touch programming. Options for the instruments
include a 4-20 mA output, and improved accuracies. There is also a low cost
weatherproof cover available for outdoor applications.
Example
A3110-06
Description
Model
A
Round Panel Mount Housing
3
LED display, process arch, LCD
Display
4
LED display, process arch, OLED
Control
1
Control 2 SPDT relays
0
None
Transmitter
1
4-20 mA
0
1%
Accuracy
1
0.50%
- 01 0 – 0.50”
- 02 0 – 1”
- 03 0 – 2”
- 04 0 – 3”
- 05 0 – 4”
- 06 0 – 5”
- 07 0 – 8”
- 08 0 – 10”
- 09 0 – 15”
- 10 0 – 20”
Range
- 11 0 – 30”
Maximum Pressure:
Ranges
≤
4” w.c. = 2 PSI; Ranges
≥
5” w.c. = 10 PSI
Media compatibility:
Air and compatible non combustible, non corrosive gasses
Accuracy*:
Axxx0-xx - 1.00%; Axxx1-xx - 0.50%
Temperature Ranges:
Compensated:
-10° to 140°F (-23° to 60°C)
Operating:
-10° to 140°F (-23° to 60°C); A3: 10° to 140°F (-12° to 60°C)
Thermal Effect*:
+/- 0.012% FS/°F
Output Signal:
4-20 mA (option)
1. INTRODUCTION
1.1 Model Number Configuration
1.2 Specifications