30
NRG 16-51, NRG 17-51, NRG 19-51 - USA - Installation & Operating Manual -
850692-00
Bringing into service, fault indications and troubleshooting
You can find information on bringing into service, faults and troubleshooting in the Installation &
Operating Manual of the NRS 1-51 level switch.
Removing the NRG 1..-51 level electrode
1. Undo the screw
v
.
Fig. 20
2. Detach the upper part
x
of the connector from the level electrode.
3. To dismantle the equipment, unscrew the electrode thread
0
,
Fig. 12
, when it has
cooled down and is no longer under pressure.
Removing the NRG 1..-51F level electrode
1. Undo the screws
b
of the terminal box and take off the cover
d
.
Figs. 15, 16
2. Disconnect the wires from the terminal strip and pull the cables out of the cable gland.
3. To dismantle the equipment, unscrew the electrode thread
0
,
Fig. 12
, when it has cooled
down and is no longer under pressure.
Taking out of service
DANGER
Danger to life! Escaped hot steam can cause scalding.
Hot steam or hot water can escape suddenly if the level electrode is unscrewed under
pressure.
■
Reduce the boiler pressure to 0 psi (0 bar) and check the pressure before unscrew-
ing the level electrode.
■
Only remove the level electrode at
0 psi (0 bar) boiler pressure
.
WARNING
The hot level electrode can cause severe burns.
The level electrode gets very hot during operation.
■
Always let the level electrode cool down before performing installation and mainte-
nance work.
■
Only remove level electrodes that have cooled down.
Proceed as follows:
1.
Reduce the boiler pressure to 0 psi (0 bar).
2.
Allow the level electrode to cool to room temperature.
3.
Switch off the supply voltage.
4.
Pull out the connector.
5.
Then remove the level electrode.