8
NRG 16-51, NRG 17-51, NRG 19-51 - USA - Installation & Operating Manual -
850692-00
Usage for the intended purpose
NRG 1...-51 level electrodes are used in conjunction with the NRS 1-51 level switch as a
high-level alarm for steam boilers and hot water installations.
A high-level alarm prevents the defined high water (HW) level from being exceeded and switches
off the feedwater supply, for example, to achieve this.
The equipment has been tested and approved for use in the scope governed by the following
directives and standards:
Standards:
■
UL 60730-1 and CAN/CSA E60730-1
General Requirements for Automatic Electrical Controls
■
UL 60730-2-15 and CAN/CSA E60730-2-15
Requirements for Automatic Electrical Water Level Sensing Controls
Applicable directives and standards
Improper use
There is a danger of death due to explosion if the equipment is used in potentially
explosive atmospheres.
Do not use the equipment in potentially explosive atmospheres.
Do not bring any equipment into service that does not have its own specific rating
plate.
The rating plate indicates the technical features of the equipment.
Admissible system components
According to UL 60730-2-15, the NRG 1...-51 level electrode can be operated with the NRS 1-51
level switch and regarded as a protective control.
To ensure proper use in all applications, please also read the Installation & Operating
Manuals for the system components used.
■
You can find the latest Installation & Operating Manuals for other system compo-
nents on our website:
http://www.gestra.com