13
NRGS 15-1 - USA - Installation & Operating Manual -
850690-00
Technical data
Cable entry/electrical connection
3 cable glands with integrated cable clamp (M 16).
1 2-pole terminal strip for power supply.
1 12-pole terminal strip for connecting the control cables.
Terminal strips are detachable screw-type models with conductor size ≥ AWG 16 (≤ 1.5 mm).
Protection
NEMA type 4 according to NEMA 250
IP 65 according to EN 60529
Protection class
Class II with functional ground via boiler wall
Installation class
3
Overvoltage category
CAT III
Admissible ambient temperature
at power-on 32 ° ... 158 °F (0 ° ... 70 °C)
during operation 14 ° ... 158 °F (-10 ° ... 70 °C)
Transport temperature
-4 ° ... +176 °F (-20 ° ... +80 °C) (< 100 hours), only switch on after a defrosting period of 24
hours.
Storage temperature
-4 ° ... 158 °F (-20 ° ... +70 °C), only switch on after a defrosting period of 24 hours.
Relative humidity
Max. 95%, no moisture condensation
Weight
Approx. 3.08 lb (1.4 kg)
Other information
Independently mounted Type 1.B action operating control
Pollution degree 2, impulse voltage 4000 V