NRGS 15-1 - USA - Installation & Operating Manual -
850690-00
Setting functions
Setting the response sensitivity
The default sensitivity is factory-set at ≥ 5 ppm (10 µS/cm).
If the boiler water has lower conductivity than 5 ppm (10 µS/cm) at 77 °F (25 °C), please change
the sensitivity using the code switch
&
. The code switch
&
is located on the electronic circuit
board (see
Fig. 5
) and is set using a thin blade screwdriver.
The sensitivity can be set as follows:
Code switch
White toggle switch
Sensitivity
Sensitivity ≥ 5 ppm (10 µS/cm) at 77 °F (25 °C)
(default)
ON
1 2 3
5
4
6 7 8 910
ON
1 2 3
5
4
6 7 8 910