31
NRGS 15-1 - USA - Installation & Operating Manual -
850690-00
Bringing into service
Checking switchpoints and functions
Danger
The terminal strips of the level switch are live during operation!
There is a risk of serious injury due to electric shock.
Always cut off power to the level switch before working on it or on the terminal
strips (installation, removal, connecting cables).
Start
Action
Display
Function
Switch on supply voltage.
ON LED lights up
LEDs
1
,
2,
3
,
4
light up depending on the water level.
MIN water level = electrode rod 1
Drain water until it is below the MIN level.
Electrode rod 1 is exposed.
LED 1 lights up red
After 1s: MIN output contact 4/5 closed,
4/6 open.
Fill tank until water is above the MIN level.
Electrode rod 1 is immersed.
LED 1 is not lit
After 1s: MIN output contact 4/5 open,
4/6 closed
MIN water level 2 = electrode rod 2
Drain water until it is below MIN level 2.
Electrode rod 2 is exposed.
LED 2 lights up red
After 1s: MIN output contact 7/8 closed,
7/9 open.
Fill tank until water is above MIN level 2.
Electrode rod 2 is immersed
LED 1 is not lit
After 1s: MIN output contact 7/8 open,
7/9 closed.
MAX water level = electrode rod 4
Fill tank until water is above the MAX
level. Electrode rod 4 is immersed.
LED 4 lights up red
After 3s: MIN output contact 13/14
closed, 13/15 open.
Drain water until it is below the MAX level.
Electrode rod 4 is exposed.
LED 4 is not lit
After 3s: MIN output contact 13/14 open,
13/15 closed.