35
NRGS 15-1 - USA - Installation & Operating Manual -
850690-00
Taking out of service
DANGER
Danger to life from scalding caused by escaping hot steam.
Hot steam or water can escape suddenly if the level electrode is unscrewed under
pressure.
■
Reduce the boiler pressure to 0 psi (0 bar) and check boiler pressure before unscrew-
ing the level electrode.
■
Only remove the level electrode at
0 psi (0 bar) boiler pressure
.
WARNING
The hot level electrode can cause severe burns.
The level electrode gets very hot during operation.
■
Always let the level electrode cool down before performing installation and mainte-
nance work.
■
Only remove level electrodes that have cooled down.
Removing the level switch
Proceed as follows:
To remove the level switch, take it out of service and
cut off the power supply
.
1. Undo the cover screws
(
and remove the cover
)
.
(Figs. 4, 5)
2. Disconnect all connecting cables from terminal strips
6
,
8
and pull the cables out of the
cable glands.
3. Make sure that the level switch is cold and not under pressure before removal.