2
Electrical Connection
– continued –
Design “c”/“d”
Wiring is effected via the 32 pole screw-type connector.
Use screened two-core cable, conductor size 0.5 mm
2
, max. cable length 50 m for the supply of the
level transmitter.
Wiring diagram for design “c”/“d”
4
3
2
5
1
Fig. 4
Attention
■
Protect the control circuit with a 2.5 A (slow blow) fuse.
■
Connect screen only to the assigned terminal of the switch.
■
The screen must not make any other electrical contact.
■
When switching off inductive loads, voltage spikes are produced that may impair
the operation of control and measuring systems. Inductive loads should therefore be
provided with commercial arc suppressor RC combinations, e. g. 0. µF/ 00 Ω.