Attention
Before carrying out the fault diagnosis please check:
Supply voltage:
Is the temperature transmitter or temperature switch supplied with the mains voltage
specified on the name plate?
Wiring:
Is the wiring in accordance with the wiring diagram?
Troubleshooting
Indication, diagnosis and remedy
Faults indicated by the seven-segment display (TRS 5-52)
or the seven-segment display on the right (TRV 5-40, TRS 5-50)
Error code
Error
Remedy
E.xxx
Temperature sensor defective, temperature
reading too low.
Check whether the temperature sensor outputs cor-
rect readings (see
Fig. 12
). If there are any deviations
please replace the measuring element with a new one.
Check the sensor lines (short circuit, interruption?).
E.xxx
Temperature sensor defective, temperature
reading too high.
Measure the fluid temperature
Use table
Fig. 12
to ascertain the current temperature of the fluid via the resistance value of the Pt 100.
1. Take cover
d
off the terminal box .
2. Connect test cable directly to the measuring element
e
.
3. Use an ohmmeter for measuring the resistance value.
4. Look up the corresponding resistance value in the table, interpolate if necessary and read off the
temperature.
5. After measurement replace cover
d
and fix it securely in place.
°C
0
10
20
30
40
50
60
70
80
90
100
Ω/deg
0
100.00 103.90 107.79 111.67 115.54 119.40 123.24 127.07 130.89 134.70 138.50 0.385
100
138.50 142.28 146.06 149.82 153.57 157.32 161.04 164.76 168.47 172.16 175.84 0.373
200
175.84 179.51 183.17 186.82 190.46 194.08 197.70 201.30 204.88 208.46 212.03 0.361
300
212.03 215.58 219.13 222.66 226.18 229.69 233.19 236.67 240.15 243.61 247.06 0.350
400
247.06 250.50 253.93 257.34 260.75 264.14 267.52 270.89 274.25 277.60 280.93 0.338
500
280.93 284.26 287.57 290.87 294.16 297.43 300.70 303.95 307.20 310.43 313.65 0.327
600
313.65 316.86 320.05 323.24 326.41 329.57 332.72 335.86 338.99 342.10 345.21 0.315
700
345.21 384.30 351.38 354.45 357.51 360.55 363.59 366.61 369.62 372.62 375.61 0.304
800
375.61 378.59 381.55 384.50 387.45 390.38
0.295
Basic values of the precision resistors according to DIN 43760 for Pt 100.
Fig. 12
Fault code
see installation and operating manuals for temperature transmitter TRV 5-40 and for tempe-
rature switches TRS 5-50 and TRS 5-52.