26
Restart after stop
Restart after an emergency stop
The emergency stop should be reset by the same operator who activated it. The factory's
additional safety procedures must be followed.
1.
Correct the error that caused the the emergency stop.
2.
Ensure that no person can get injured.
3.
Reset the emergency stop by turning the e-stop button clockwise or pull out the
emergency stop button.
4.
Reset the emergency stop by pressing the blue Control On button on the main
cabinet AK1.
5.
Restore any broken protective stop circuits by pressing the respective reset button
(Safety gates must be closed, and light protection must be free/must not detect
anything).
Restart of Auto mode is done according to the section Auto mode0
Restart after safety stop
The factory's additional safety procedures should be followed.
1.
Ensure that no one is in the safety area.
2.
Ensure that no person can get injured.
3.
Reset the cause of the safety stop (gate, light barriers).
4.
Reset the protective stop circuitry by pressing the respective gate reset button.
5.
Restart of Auto mode is done according to the section 0Auto mode.
Restart after an error
1.
Correct the cause of the error
2.
Ensure that it is safe to resume/restart operations, that no one can get injured.
3.
Restart of Auto mode is done according to the section Auto mode.
Restart after PLC-stop
If the PLC is stopped, selections are reset in PLC and HMI and A-alarm will be triggered.
1.
Check for alarm on the HMI.
2.
Reset Emergency Stop as per section Restart after emergency stop.
3.
Automatic restart is done according to the section Auto mode.
Summary of Contents for GEV TS 121650 AR-2
Page 1: ...1 GEV TS 121650 AR 2 PFIZER ROBOTIC SYSTEMS 0011393179 010 USER MANUAL...
Page 49: ...49 Robot pendant Manual Auto mode Auto Manual mode Quick menu Key selector...
Page 52: ...52 Quick select Jogging Increments Motion mode Step mode...
Page 54: ...54 Robot 210 Home position Robot 220 Home position...