2  Application 

The KNX field line coupler (from DIN rail) is used to connect a main KNX-TP line with a secondary KNX-TP 
line, providing galvanic insulation between the two. 
The  device  filters  the  traffic  between  the  two  lines  (coupler)  or  forwards  packs  from  the  main  line  to  the 
secondary  one  (repeater).  The  coupler  can  be  used  to  connect  a  line  to  a  main  line  or  a  main  line  to  a 
backbone line.  
 
The device is equipped with: 
 

 

1.  Main line status LED 

off 

 main line error or device not connected to the bus 

fixed green 

 main line functioning 

fixed green and red 

 manual function active 

 

2.  Sub line status LED 

off 

 sub line error or line not connected to the bus 

fixed green 

 sub line functioning 

 

3.  Main line data traffic status LED 

off 

 no data traffic on the main line 

flashing green 

 data traffic in progress on the main line 

flashing red 

 data transmission error on the main line 

 

4.  Sub line data traffic status LED 

off 

 no data traffic on the sub line 

flashing green 

 data traffic in progress on the sub line 

flashing red 

 data transmission error on the sub line 

 

5.  Status LED for forwarding telegrams with group addresses 

off 

 different telegram forwarding rules between main and sub line 

fixed green 

 telegram forwarding according to the filter table 

fixed green and red 

 transmit all telegrams 

fixed red 

 block telegrams 

 

6.  Status LED for forwarding telegrams with physical addresses 

off 

 different telegram forwarding rules between main and sub line 

fixed green 

 telegram forwarding according to the filter table 

fixed green and yellow 

 transmit all telegrams 

fixed yellow 

 block telegrams 

 

Summary of Contents for CHORUS GW 90708A

Page 1: ...KNX field line coupler GW 90708A Technical Manual ...

Page 2: ...peater 6 3 General Menu Coupler 7 3 1 Parameters 7 4 Main line menu Coupler 8 4 1 Parameters 8 5 Sub line Menu Coupler 11 5 1 Parameters 11 6 General menu Repeater 14 6 1 Parameters 14 7 Main line menu Repeater 15 7 1 Parameters 15 8 Sub line menu Repeater 17 8 1 Parameters 17 ...

Page 3: ... are set and configured with the aid of the ETS configuration software The GW90708A device has two separate ETS application programmes based on the function to be performed Coupler KNX Line coupler S 1 0 Repeater KNX Line repeater S 1 0 This manual describes the parameters relative to both application programmes ...

Page 4: ...Main line data traffic status LED off no data traffic on the main line flashing green data traffic in progress on the main line flashing red data transmission error on the main line 4 Sub line data traffic status LED off no data traffic on the sub line flashing green data traffic in progress on the sub line flashing red data transmission error on the sub line 5 Status LED for forwarding telegrams ...

Page 5: ... 2 and the status LED for forwarding telegrams with group addresses 5 turn on green and red whereas the status LED for forwarding telegrams with physical addresses 6 turns on yellow and green Release the button key and press it again for at least 3 seconds until the LEDs turn off briefly and then turn on again according to the configuration set for normal device operation Reset of parameters and p...

Page 6: ...ress X Y Z Transmission and repetition of telegrams on a line without a filter Division of a line into max 4 independent line segments with max 3 repeaters connected in parallel for each line Each line segment requires its own KNX power supply PS ...

Page 7: ...ng the button key or automatically after the preset time defined via the parameter Fallback time for manual operation elapses The values that can be set are 10 min 1 hour default value 4 hours 8 hours 3 1 2 Manual function This parameter can be used to define the manual function activated by the button key the manual function makes it possible to temporarily change the telegram forwarding rules Th...

Page 8: ...roups route physical filter groups physical route configure by selecting configure all the other parameters present in the configuration menu will be configurable If any of the other values is selected the parameters can be consulted but their value is preset and cannot be changed 4 1 2 Group telegrams This parameter is used to define the rule for forwarding telegrams whose recipient has a group a...

Page 9: ...Repetition if errors on main line This parameter is used to enable the repetition of telegrams generated by the coupler if there is a transmission error on the main line e g due to a receiver failure in particular this parameter refers to telegrams whose recipient has a physical address The values that can be set are no no repetition in case of an error normal default value in case of an error the...

Page 10: ...d or not 4 1 8 Send confirmation on own telegrams This parameter is used to enable the function for automatically sending the confirmation telegram ACK for the telegrams sent by the device on the main line The values that can be set are no default value when the device sends a telegram on the main line it does not send the confirmation telegram ACK for that telegram the telegram will be confirmed ...

Page 11: ... the sub line to the main line from a preset list of rules based on the selection made the subsequent parameters are configured as a result The values that can be set are groups filter physical block groups physical filter default value groups route physical filter groups physical route configure by selecting configure all the other parameters present in the configuration menu will be configurable...

Page 12: ...ter is used to define the rule for forwarding telegrams whose recipient has a physical address telegrams that are used during point point communication for example when programming a device The values that can be set are transmit all for testing only all telegrams are forwarded block no telegrams are forwarded filter default value only the telegrams with an address present in the filter table are ...

Page 13: ... default value the device sends the confirmation telegram for only the telegrams transmitted on the sub line that are forwarded on the main line always the device sends the confirmation telegram for all telegrams on the sub line regardless if they are forwarded or not 5 1 8 Send confirmation on own telegrams This parameter is used to enable the function for automatically sending the confirmation t...

Page 14: ...ing the button key or automatically after the preset time defined via the parameter Fallback time for manual operation elapses The values that can be set are 10 min 1 hour default value 4 hours 8 hours 6 1 2 Manual function This parameter can be used to define the manual function activated by the button key the manual function makes it possible to temporarily change the telegram forwarding rules T...

Page 15: ...et are group physical route default value configure by selecting configure all the other parameters present in the configuration menu will be configurable Selecting group physical route the parameters can be consulted but their value is preset and cannot be changed 7 1 2 Physical telegrams This parameter is used to define the rule for forwarding telegrams whose recipient has a physical address tel...

Page 16: ...mum of 3 attempts reduced default value in case of an error the telegram is repeated only once 7 1 5 Telegram confirmations on main line This parameter defines the rule for confirming telegrams ACK transmitted on the main line The values that can be set are if routed the device sends the confirmation telegram for only the telegrams transmitted on the main line that are forwarded on the sub line al...

Page 17: ... set are group physical route default value configure by selecting configure all the other parameters present in the configuration menu will be configurable Selecting group physical route the parameters can be consulted but their value is preset and cannot be changed 8 1 2 Physical telegrams This parameter is used to define the rule for forwarding telegrams whose recipient has a physical address t...

Page 18: ...maximum of 3 attempts reduced default value in case of an error the telegram is repeated only once 8 1 5 Telegram confirmations on line This parameter defines the rule for confirming telegrams ACK transmitted on the sub line The values that can be set are if routed the device sends the confirmation telegram for only the telegrams transmitted on the sub line that are forwarded on the sub line alway...

Page 19: ...19 LAST REVISION 02 2016 code 7 01 8 063 3 ...

Reviews: