59
7.2.2. CONNECTION OF THE DEVICE POWER SUPPLY
Protection devices
Each charging station must be protected upstream by circuit breaker protection and residual current devices
required by the low voltage electrical system standard. In particular, each individual station must be protected
upstream by a Type A residual current circuit breaker 30 mA + miniature circuit breaker (the choice of device must
be suitable for the power level and the power supply of the recharging station; protection against DC leakage is
provided by the DC Leakage 6 mA device built into the products).
Wiring requisites
The connection must satisfy some requirements:
Connection specifications
Type of connection
Single-phase/
three-phase
Number of wires
2P+E/3P+N+E
Rated current
Up to 32A
Maximum wire diameter
10mm
2
Connection procedure
1. Open the casing as shown in the figure.
3
4
2
3
4
2
Summary of Contents for JOINON I-CON PREMIUM GWJ3201A
Page 15: ...15 Fissaggio mediante staffe supporto palo GW46551 ...
Page 41: ......
Page 55: ...55 Fixing with the aid of support brackets on pole GW46551 ...
Page 81: ......
Page 95: ...95 Fixation sur pattes support du poteau GW46551 ...
Page 121: ......
Page 135: ...135 Fijación mediante grapas de soporte poste GW46551 ...
Page 161: ......
Page 175: ...175 Befestigung mit Masthalterungen GW46551 ...
Page 201: ......
Page 215: ...215 Fixarea cu ajutorul suporturilor de susținere a stâlpului GW46551 ...
Page 241: ......
Page 255: ...255 Rögzítés oszlopra való tartókengyelekkel GW46551 ...
Page 281: ......
Page 295: ...295 Bevestiging met behulp van steunbeugels paal GW46551 ...
Page 321: ......
Page 322: ......
Page 323: ......