ECturn/ECturn Inside
16
Mechanical contact
5.4.2 Monitoring opening
X
Set the parameters:
à
s1
(safety closing) to
0 o
for “no SIS”.
à
s3
(safety opening) to
01
for “SIO”.
à
Te
(testing) to
01
for “testing with 24V”.
1
GND
13
SIO
10
TST
4
24VSENS
SIO
GC335 Master
BS
6
5
4
3
+ 2
- 1
60mA
Test
GC335
Slaves
1
1
Door transmission cable
5.4.3 Monitoring closing
X
Set the parameters:
à
s1
(safety closing) to
01
for “SIS” or to
0 2
for “SIS
and K”.
à
s3
(safety opening) to
0 o
for “no SIO”.
à
Te
(testing) to
01
for “testing with 24V”.
1
GND
11
SIS
10
TST
4
24VSENS
SIS
GC335 Master
BGS
6
5
4
3
+ 2
- 1
60mA
Test
GC335
Slaves
1
1
Door transmission cable
6
Mechanical contact
à
The input KB is active in the AU and NA operating modes.
à
When activated, the door opens.
à
On activation the output of the mechanical contact is closed (24 V applied at the KB input).
à
The mechanical contact function can also be activated via the WRB-5 receiving module, channel 2 (see 8.1.2,
à
Do not operate the mechanical contact continuously since the drive will otherwise not be able to switch off auto-
matically in the event of a supply voltage failure and the rechargeable battery of the drive will become discharged.
à
Do not connect electrical loads to the terminal 24VKB because otherwise the rechargeable battery cannot
be charged.
à
The hold-open time when actuating via KB can be set separately.
à
Parameter
Os
(hold-open time KB).
à
An activation delay can be set for contact sensor KB:
à
Parameter
a I
(opening delay).
WARNING
Danger of injury due to impact and crushing!
If there is a rechargeable battery connected, the drive opens after activation KB even when mains voltage
is switched off.
X
Disconnect the rechargeable battery.
6.1 Key switch
à
SCT key switch, single-pole, flush-mounted, AS500 without Euro
profile half cylinder, mat. no. 117996
à
Accessories:
à
Euro profile half cylinder, mat. no. 090176
à
Additional contact, mat. no. 024467
20
K
3
2
KB
B
4V