IQ lock AUT, EL / EL DL, EM / EM DL, C / C DL, M / M DL
28
Wiring diagrams
6.5 IQ lock EL with EMD (-F, -I), TZ 320 SN and activation
X
Follow the installation instructions for IQ lock.
X
Heed the wiring diagram for EMD, EMD-F, EMD Invers.
X
Heed the wiring diagram for GEZE SecuLogic RWS (TZ 320).
X
Disconnect the internal programme switch of the door drive.
X
For 2-leaf door drives connect the control to the active leaf.
X
Set the parameters on the control DCU2, DCU2-F, DCU-I:
à
with DPS: Set
a1
to
1 8
(day-night switchover), parameter
®®
(bar message) to
0 2
(electric strike) and
TO
(electric strike) to
0 3
(motor lock).
à
with ST220: Set Signals
Output signals
PA1 to day/night switchover.
Set Signals
Input signals
Bolt contact type to electric strike.
Set Door parameters
Electric strike type to motor lock.
The following settings must be made on the TZ 320:
X
Set Output 1 to “BA drive”.
X
Set Output 2 to “Activation drive”.
à
Voltage supply of the MST 210 from separate power supply NT 19.2-24 or from the DCU2 control