UFO-NT

11

"Open" and "close" safety sensor

5.1.2  Monitoring opening

Standard operation

 

X

Setting the "Contact type" parameter:

 

à

DPS: Set 

s3

 to 

0 2

 ("NC") 

(default setting).

 

à

ST220:  Set the "Input signals", "SI3 – terminal SIO", 

"SI3 contact type" to "NC" 

(default setting).

 

à

S1, S2:  Set parameter 9 to 02 (NC).

Energy-saving mode

 

X

Setting the "Contact type" parameter;

 

à

DPS: 

Set 

s3

 to 

0 3

 (frequency)  

.

 

à

ST220:  Set the "Input signals", "SI3 – terminal SIO", 

"SI3 contact type" to "frequency".

 

X

Setting the Function parameter:

 

à

DPS: 

Set 

f3

 to 

0 5

 (SIO stop) or  

0 6

 (SIO stop SF-GF).

 

à

ST220:  Set the "Input signals", "SI3 – terminal SIO", 

"SI3 function" to "SIO stop" or 

"SIO stop SF GF".

 

à

S1, S2:  Set parameter 10 to 05 (SIO stop) or 

06 (SIO stop SF GF).

1

13

10

4

SIO 

SIO 
GND
24VSENS
TST

S

E

GY 

2

1

4

3

5

BN
BK
BU

WH

SIGNAL

24V

SIO

GND

SIS

100mA

2

1

3

4

Opposite hinge side

Hinge side

Door transmission cable

GC 338 interface module

Summary of Contents for UFO-NT F

Page 1: ......

Page 2: ...t detector 19 7 2 Push button floating normally opened contact 19 8 Contact sensor outside 20 8 1 GC 302 R radar movement detector 20 8 2 Push button floating normally opened contact 20 9 Radio control 21 9 1 Radio reception board WRB 5 21 9 2 Insert the radio reception board WRB 5 to the control circuit board DCU800 21 9 3 Transmitting module WTM 21 10 Push And Go 22 11 Configurable inputs 22 11 ...

Page 3: ...ion via system cable RS485 40 18 Motor 40 19 Control 41 20 Commissioning and service 42 20 1 Commissioning 42 20 2 Teaching run 42 20 3 Teaching a 1 leaf system 43 20 4 Teaching a 2 leaf system 44 20 5 Forces and speeds 45 21 Disconnected mode 45 22 Free swing function 46 23 Resilience to external influences or load due to wind pressure 46 24 Door closer operation 46 25 Low energy mode 47 26 Servo...

Page 4: ...s additional information X X Symbol for an action This means you have to do something X X If there are several actions to be taken keep to the given order Compliant with EN 16005 Symbol in a table or in information concerning safety sensors Not compliant with EN 16005 Symbol in a table or for a piece of information on sensors that do not cor respond to EN 16005 Fire protection door Symbol for fire...

Page 5: ...d similar electrical appliances Particular requirements for drives for gates doors and windows à à Accident Prevention Regulations in particular BGV A1 VBG1 General Regulations BGV A3 VBG4 Electrical Installations and Resources 1 2 Installation information X X Only use the cables prescribed in the cable plan provided Cables must be shielded in compliance with the wiring diagram X X Always use insu...

Page 6: ...outside KB Mechanical con tact KI Contact sensor inside LK Luster terminal LS Exit only MPS Mechanical programme switch NA Night PA Configurable output PE Configurable input RBM Radar movement detec tor RES Reset switch RM Bolt message RSZ Smoke control unit RS485 Communication signal to DPS and second drive OFF OFF mode of operation SF Passive leaf STOP Stop SCR Screen SO Opening safety sensor SI...

Page 7: ...UFO NT 7 Supply terminals 4 Supply terminals DCU800 1 2 24V GND 6 1 RS485 passive leaf 2 FREE ...

Page 8: ... 8 7 6 0 2 4 2 1 57 56 55 2 1 98 97 96 95 53 52 51 KB 4 10 4 1 11 10 4 1 13 36 35 1 33 32 31 2 1 KI KA SIS SIO N N TOE 46 46 44 45 CANL CANH GND CAN ISO CAN KA DPS RS485 DCU106 2 1 Socket DCU103 2 FREE Optional CAN interface DCU103 Mat no 119952 S1 Terminating resistor ON OFF ...

Page 9: ...nking range of the sensor strip SIO is set automatically during the teaching procedure If necessary it can be changed with DPS or ST220 via the service menu with à à DPS Set the parameter aB to the desired wall blanking range 1 to 99 à à ST220 Set Input signals SI3 terminal SIO1 SI3 wall blanking area to the desired value 1 to 99 5 1 Safety sensor strip pair GC 338 X X Follow installation instruct...

Page 10: ...à ST220 Set the Input signals SI1 terminal SIS SI1 contact type to frequency and SI3 terminal SIO SI3 contact type to frequency X X Setting the Function parameter à à DPS Set f1 to the desired function and f3 to 0 5 SIO stop or 0 6 SIO stop SF GF à à ST220 Set the Input signals SI1 terminal SIS SI1 function to the desired function and SI3 terminal SIO SI3 function to SIO stop or SIO stop SF GF S E...

Page 11: ...er à à DPS Set s3 to 03 frequency à à ST220 Set the Input signals SI3 terminal SIO SI3 contact type to frequency X X Setting the Function parameter à à DPS Set f3 to 0 5 SIO stop or 0 6 SIO stop SF GF à à ST220 Set the Input signals SI3 terminal SIO SI3 function to SIO stop or SIO stop SF GF à à S1 S2 Set parameter 10 to 05 SIO stop or 06 SIO stop SF GF 1 13 10 4 SIO SIO GND 24VSENS TST S E GY 2 1...

Page 12: ...e Input signals SI1 terminal SIS SI1 function to the desired function à à S1 S2 Set parameter 8 to the desired function 1 11 10 4 SIS SIS GND 24VSENS TST S E GY 2 1 4 3 5 BN BK BU WH SIGNAL 24V SIO GND SIS 100mA 1 2 3 4 1 Opposite hinge side 2 Hinge side 3 Door transmission cable 4 GC 338 interface module 5 2 Safety sensor GC 342 à à Safety sensor GC 342 à à Follow installation instructions GC 342...

Page 13: ...to NC default setting X X Setting the Function parameter à à DPS Set f1 to the desired function and f3 to 0 5 SIO stop or 0 6 SIO stop SF GF à à ST220 Set the Input signals SI1 terminal SIS SI1 function to the desired function and SI3 terminal SIO SI3 function to SIO stop or SIO stop SF GF 5 2 2 Monitoring opening 1 SIO 13 1 GND 4 24VSENS 10 TST SIO UB UB COM SIO 60 mA Test SIS GC 342 BS BN GN YE ...

Page 14: ...à DPS Set Te to 0 2 testing with GND à à ST220 Set Output signals Testing SI to Testing with GND à à Max 6 modules in series 5 3 1 Monitoring closing and opening X X Setting the Contact type parameter à à DPS Set s1 to 0 2 NC and s3 to 0 2 NC default setting à à ST220 Set the Input signals SI1 terminal SIS1 SI1 contact type to NC and SI3 terminal SIO1 SI3 contact type to NC default setting X X Set...

Page 15: ...ration DIP1 ON 1 GND 13 SIO 10 TST 4 24VSENS SIO GC 334 BS WH YE BN GN BU RD GC 334 Module 60mA 1 PK VT 1 Door transmission cable 5 3 3 Monitoring closing X X Setting the Contact type parameter à à DPS Set s1 to 0 2 NC default setting à à ST220 Set the Input signals SI1 terminal SIS1 and SI1 contact type to NC default setting X X Setting the Function parameter à à DPS Set f1 to the desired functio...

Page 16: ...allation instructions à à Accessories à à GC 332 adapter mat no 124035 à à Spot finder mat no 112321 X X Use the reference body mat no 120190 to set the detection field X X Always install the master module near the hinge connection with the drive control takes place at the master module X X Connect max 7 slave modules to one master module X X Open the configuration bridge at the last slave module ...

Page 17: ...ion parameter à à DPS Set f1 to the desired function and f3 to 0 5 SIO stop or 0 6 SIO stop SF GF à à ST220 Set the Input signals SI1 terminal SIS1 SI1 function to the desired function and SI3 terminal SIO1 SI3 function to SIO stop or SIO stop SF GF GC 335 Slaves 1 GND 13 SIO 10 TST 4 24VSENS GC 335 Master BGS SIO 1 GND 11 SIS 10 TST 4 24VSENS SIS WH BN GY GN PK YE 6 5 4 3 2 1 60mA Test GC 335 Mas...

Page 18: ... KB is active in the AU LS and NA modes of operation à à In the case of 2 leaf systems the mechanical contact can be connected to the active leaf control or to the pas sive leaf control à à Upon activation the active leaf opens and if switched on the passive leaf opens à à During activation the output of the mechanical contact is closed and 24 V is applied at the KB input NO con tact 0 V is applie...

Page 19: ...a to the desired delay time 0 s 9 s à à ST220 Use the or keys to set Signals Input signals KI or KI delay to the desired delay time 0 s 9 s and press the key 7 1 GC 302 R radar movement detector à à Upon activation the output of the GC 302 R is closed 24 V applied to the KI input à à Set the Contact type parameter with à à DPS Set ci to 01 default setting à à ST220 Set the Signals Input signals KI...

Page 20: ...tivation delay time can be set for the KA input This time is added to the general activation delay time opening delay Set the parameters with à à DPS Set aa to the desired delay time 0 s 9 s à à ST220 Use the or key to set Signals Input signals KA KA delay to the desired delay time 0 s 9 s and press the key 8 1 GC 302 R radar movement detector à à For information see GC 302 R KI à à Upon activatio...

Page 21: ...rol Only insert the radio reception board WRB 5 into the DCU800 control when powered down 9 2 Insert the radio reception board WRB 5 to the control circuit board DCU800 X X Press spacer 2 onto the control circuit board DCU800 3 X X Set the radio reception board WRB 5 1 onto spacer 2 and connector strip 4 X X Move the aerial to the right position see figure 9 3 Transmitting module WTM Transmitting ...

Page 22: ...parameters Push And Go to the opening range 1 20 to start the automatic opening function or set Push And Go to 0 to disable the function Set the Movement parameters Hold open times Push And Go to the desired hold open time 0 60 s 11 Configurable inputs à à Various special functions are assigned to the configurable inputs PE1 PE2 and PE3 see 27 Service menu The contact type required for the desired...

Page 23: ...1 PE2 or PE3 can be used to connect an alarm contact which can be used to monitor a closed key switch housing In the case of a closed housing the contact is closed and 24 V is applied to input PE1 PE2 or PE3 When the alarm contact opens 0 V is applied to input PE1 PE2 or PE3 In this case the door remains closed and locked If the contact is interrupted KB is not evaluated in the NA LS AU mode of op...

Page 24: ...PS Set e1 e2 or e3 to 0 8 contact sensor inside or to 0 9 contact sensor outside à à ST220 Set PE1 function PE2 function or PE3 function to P KI actuation NO or P KA actuation NO à à For more information see chapter 7 Contact sensor inside or chapter 8 Contact sensor outside à à The contact sensors can either be connected to terminal 2 24 V or terminal 4 24 VSens 11 7 Switch function 11 7 1 Genera...

Page 25: ... 53 PE3 PE3 GF oder 11 8 Control reset à à The control can be reinitialised via the configurable inputs After the push button has been activated the drive behaves as though the mains voltage has been switched on à à Set the parameters with à à DPS Set e1 e2 or e3 to 13 reset switch à à ST220 Set PE1 function PE2 function or PE3 function to Reset switch NO 51 PE1 2 24V PE1 GF 52 PE2 PE2 GF oder 53 ...

Page 26: ...be connected to monitor the input The terminating resistor must be directly connected to the switch contact à à Set the Contact type parameter with à à DPS e2 or e3 to 1 2 or 2 0 à à ST220 Set Signals Input signals PE2 or PE3 PE2 function or PE3 function to Stop 12 kOhm or Stop 20 kOhm 12 kΩ oder 20 kΩ E2 E3 12 Stop 12 kΩ NO E2 E3 20 Stop 20 kΩ NO 52 PE2 2 24V PE2 PE3 oder 53 PE3 2 24V 11 11 Close...

Page 27: ...eaf controller 12 Configurable outputs Various switching functions are assigned to configurable outputs PA1 and PA2 see chapter 27 Service menu à à To operate the DPS DPS see chapter 27 4 DPS DPS à à To operate the service terminal ST220 see chapter 27 1 Service terminal ST220 The state of the drive to which the ST220 is connected is displayed X X Press the button X X Select Active leaf para or Pa...

Page 28: ...fault à à ST220 Set PA1 function to MPS fault 12 1 4 Warning signal à à The function is used to cyclically switch on off a customer signal device while the door is opened or closed à à Observe the maximum permissible total current draw of the control à à Set the parameters with à à DPS Set a1 to 0 5 Warning signal à à ST220 Set PA1 function to Warning signal 1 24 V DC signal transmitter supplied o...

Page 29: ... message 12 1 6 Door status message à à The function is used to signal the door status e g to a customer building control centre à à Message function door mode 08 Closed and locked 09 Closed 10 Not closed 11 Open 12 Off 13 Night 14 Exit only 15 Automatic 16 Hold open 18 Day Night changeover 20 Maintenance due see chapter 12 1 9 à à Set the parameters with à à DPS Set a1 to the desired message func...

Page 30: ...ion is used to mode of operation to a customer building control centre Or for switching a motor lock to day mode operation The output contact closes if the mode of operation LS AU 1 leaf DO AU 2 leaf or a motor lock is set à à Set the parameters with à à DPS Set a1 to 1 8 Day Night mode of operation message à à ST220 Set PA1 function to Day Night changeover à à Connecting a building control centre...

Page 31: ...ing fault number is displayed at DPS X X A relay for galvanic isolation must be installed for forwarding the fault message e g to a building manage ment system 1 Building control centre provided by customer 2 Signal input 3 24 V relay mat no 103352 4 Free swing diode GND 1 2 24V 55 PA1A 56 PA1B PA 57 PA2 2 1 3 4 12 2 3 Fault indication for MPS à à The function is used to switch the fault LED at th...

Page 32: ...ied electric strike 1 Free swing diode 1N4007 mat no 115293 1 GND 1 2 24V 55 PA1A 56 PA1B PA PA2 57 Bolt message RM See chapter 13 Electric strike Bolt message 12 2 6 Door status message à à The function is used to signal the door status e g to a customer building control centre à à Door modes 08 Closed and locked 09 Closed 10 Not closed 11 Open 12 Off 13 Night 14 Exit only 15 Automatic 16 Hold op...

Page 33: ...further settings see the descriptions below à à Set the parameter Electric strike type with à à DPS Set TO to the desired electric strike type see chapter 27 5 Service menu DPS à à ST220 Set the Door parameters Electric strike type to the desired type see chapter 27 3 Service menu ST220 à à Holding magnet MA 500 with counter plate mat no 024740 for the magnetic locking of emergency exit doors à à ...

Page 34: ...ations opening under sideload with direct voltage A5001 B with switch contact 145183 200 mA at 12 V 100 mA at 24 V Continuous operation 12 or 24 V DC 15 Instantaneous operation 12 48 V AC DC Fail secure electric strike standard applications doors with access control GEZE electric strike for fire protection doors GEZE electric strike type Mat no Current consump tion Voltage Functions FT500 B 144634...

Page 35: ...ains in its set operation mode but the DPS switches its own state to night GND 1 2 24V 31 TOEA 32 TOEB TOE RM 33 GND 1 2 24V 31 TOEA 32 TOEB TOE RM 33 Normally opened NC contact 13 4 Activation delay for lock switch contact If a lock switch contact is used and no electric strike or not used is selected the drive opens the door after a valid activation only after 2 5 s if the system has switched fr...

Page 36: ... operation back to automatic The OCCUPIED signs go out The door opens and the External push button is cleared again If the closed and locked door is opened manually from the inside or if a contact sensor mechanical contact KB is triggered the mode of operation also switches back to automatic The door can then be restarted by pressing KA When the WC is monitored for permanent locking the WC alarm s...

Page 37: ...à Mode of operation button The state of the drive to which the ST220 is connected is displayed X X Press the button X X Select Active leaf para or Passive leaf para using the or key and press the key For further settings see the descriptions below 16 1 Programme switch Mechanical programme switch MPS à à Connection to PE2 or PE3 à à MPS AS500 mat no 113226 MPS ST with key AS500 mat no 113227 à à M...

Page 38: ...o OFF 2 leaf opening or 1 leaf opening After reconnection to the mains the drive is in the previously set mode of operation à à It is possible to change the mode of op eration if the key switch is active or with jumper 1 44 2 1 1 44 41 42 GND 1 2 24V 42 RS485 A 41 RS485 B SCR 43 RS485 100 mA OFF 2 1 20 KB 3 24V KB 3 1 Display 1 leaf 2 leaf operation LED lights up at 1 leaf operation 2 Concealed se...

Page 39: ...d is 37 X X Press the key 3 times X X Press the key 7 times à à Permanent release of programme switch operation X X For permanent release attach a jumper between terminals 1 44 of the DPS and X X set the value 00 default setting as the password in the service menu 16 2 Setting the mode of operation using push buttons or switches à à It is possible to set the mode of operation using push buttons or...

Page 40: ...twork 2 1 3 GN BN WH GND RS485_B RS485_A GND RS485_B RS485_A RS485 GF RS485 SF 2 1 3 17 2 Connection via system cable RS485 Active leaf Passive leaf 2 2 1 1 System cable RS485 2 Control circuit board DCU800 18 Motor WARNING Danger of injury through link arm or lever arm snapping back Danger of injury from hot motor X X Disconnect motor from the control only if spring is not under tension 3 A M Enc...

Page 41: ...F board DCU801 2 Service buttons and service LEDs 3 LED 24V ext 4 Brake 5 Ventilator 6 Encoder 7 Motor 8 Temperature sensor 9 Latching action switch 10 LED solenoid valve 11 PROG 12 Slot for radio board WRB 5 13 FREE 14 24 V 15 RS485 16 Control box ...

Page 42: ...uired must be set before the teaching run see Powerturn installation instructions X X Mechanically set on drive and calibrate on the door leaf à à If Start teaching is started using the parameter menu DPS ST220 service keys the user has 1 minute to start the teaching process à à If the door is not moved within this time the drive cancels the teaching run and retains the data previously stored à à ...

Page 43: ...splay max drive related open positions The interruption of the warning signals is always shorter extending to the max open position à à If the beep continues to sound the the door leaf is in the range of the max open position 3 à à In this setting there is a possibility that the drive does not work properly or is perma nently damaged X X Carry out the teaching run again to avoid this Open manually...

Page 44: ...ion 3 à à In this setting there is a possibility that the drive does not work properly or is permanently damaged X X Carry out the teaching run again to avoid this 5 X X Move the door leaf by hand to the desired closed posi tion X X Push the input enter key The display is acknowledged Close manually L2 6 If GC 338 is installed and a wall will be taught X X Press the Teach In key on the sensor inte...

Page 45: ...position at this speed Exception The Closing latching action SC value is not a real value It does not correspond to a unit 21 Disconnected mode The doors can be manually opened even when in switched off or disconnected mode In the opening direction the spring force acts as a brake In the closing direction the door must close from the open position by means of the spring force with a slower speed T...

Page 46: ...st be set to 0 This does not apply if the door closing movement in the door closer mode is safeguarded with safety sensors The behaviour of the drive can be set so that its function corresponds to that of a mechanical door closer X X In the service menu set the Door closer mode Ts parameter to the desired behaviour in the door closer mode The speed within the torque controlled closing is set using...

Page 47: ...e à à The spring s retention force and opening force must be set to 67 N at the main closing edge à à The closing time must be set from 90 to 0 using the table below X X Once the power is connected set the value for the Braking force parameter so that the closing time is complied with in the disconnected state à à in a electrified state à à Static force on the main closing edge is 67 N X X The ope...

Page 48: ... alarm with additional torque 26 1 Servo support without fire alarm with additional torque The drive is power supported during manual door opening so that the door can easily be used manually even under difficult environmental conditions such as wind or against pressure in a stairwell The power assisted func tion is adjustable The door can be manually accelerated to the maximum speed of the low en...

Page 49: ...1 must consequently be bypassed X X Connect terminals 62 and 61 to the DCU801 with DCU800 terminals 2 and 1 X X Terminal 62 RSZ 24V with terminal 2 24V terminal 61 RSZ GND with terminal 1 GND PE1 24V 51 2 PE1 PE2 1 52 PE2 oder 2 1 Customer building control centre 2 Floating Fire alarm output WARNING Risk of injury due to high dynamic forces of the servo function with fire alarm X X Make sure that ...

Page 50: ... 0 20 s Servo duration 0 20 s Duration s 27 Service menu 27 1 Service terminal ST220 à à Service terminal ST220 mat no 087261 à à Commissioning of the drive is possible with the service terminal ST220 software version V2 1 or higher à à Connection either via 5 pin plug connector RS485 or using a 3 5 mm TRS connector with adapter cable mat no 157266 27 1 1 Operation of ST220 Key Function à à Cursor...

Page 51: ...on not when teaching is activated à à The hardware version is detected above software version 1 8 In case of a disparity after D1 or F1 the drive switches to safety shutdown and sets the error Incorrect HW SW combination Display after connection to the door control UFO NT U1 8 F0 DCU800 Automatic closed Drive type Software version V U1 8 Hardware version F0 Basic board DCU200 Mode of operation Doo...

Page 52: ...d Name Reference Mode of operation see chapter 27 3 3 Door parameters see chapter 27 3 4 Movement parameters see chapter 27 3 5 Signals see chapter 27 3 6 Diagnosis see chapter 27 3 7 Standard values see chapter 27 3 8 Reset DCU8 see chapter 27 3 9 Start teaching see chapter 27 3 10 Default setting see chapter 27 3 11 Delete maintenance see chapter 27 3 12 Password see chapter 27 3 13 Language see...

Page 53: ...tion à à When the standstill posi tion is reached after manual opening if drive then wants to close Electric strike type No electric strike Fail secure Fail safe Motor lock Electric strike type drive has no closing force before opening Working close pres sure Static close pressure Motor close pressure Drive has closing force before opening Opening delay Day Value 0 s 0 1 min 0 s 0 1 Max 90 s 0 1 O...

Page 54: ... the obstacle in the opening range Obstacle motor On Drive presses against obstacle in the opening range Obstacle motor Off Drive presses against obstacle in the opening range and reduces motor current to 0 A Free swing function no yes For doors without external loads such as wind or pres sure the parameter free swing function can be activated in order to enable forced closing movement of the door...

Page 55: ...in 0 s max 60 s With activation KI KA 2 leaf Opening AU So Setting on GF control 1 leaf Winter Value 1 s min 0 s max 60 s With activation KI KA 1 leaf Drive AU Wi AU So 2 leaf Opening AU So Setting on GF control Authorised contact Value 1 s min 0 s max 60 s For activation by KB Close delay GF EN16005 DIN18650 min 0 s 0 s both leaves close simultane ously 01 15 s The active leaf closes some time af...

Page 56: ...h main closing edges Push and Go Value 0 min 0 max 20 0 No Push And Go 1 20 Push And Go Response range referenced to maximum opening range 100 Adj opening angle Value 0 degrees min 9 degrees max 9 degrees The value is only for fine adjust ment The value is taught during the teaching run and then cor responds to point 0 This allows it to be adjusted manually and again subsequently corre sponds to p...

Page 57: ...ensor close triggers the drive reacts as for activation KA SIS stop If the safety sensor close trig gers the drive stops SIS manual not active active Closing safety sensor active inactive when closing after manual opening in door close mode SI3 terminal SIO current state SI3 terminal SIO Z not active K NC F SIO stop SI3 Contact type not used NC Frequency Parameter sets the use of the safety sensor...

Page 58: ... Z not active K NO contact A 0 1s KI contact type not used NO contact NC The input KI is active in AU and LS mode With 2 leaf assemblies the contact sensor inside can be connected to the active leaf control or to the passive leaf control Upon activation the ac tive leaf opens and if switched on the passive leaf opens Ac tive in every mode of operation when the door is not closed KI delay Value 0 s...

Page 59: ... over summer For the connection of a push button for the summer function Switch over winter For the connection of a push button for the winter function Only for switching over from open 1 leaf to 2 not for actually opening the door Sabotage NC Permanently switched If the contact is interrupted KB is not evaluated in the mode of operation night time All other functions remain the same Closed positi...

Page 60: ...ening When the push button is pressed once the drive opens the door and closes after the hold open time has expired When the push button is pressed again within the hold open time the drive closes the door without waiting for the hold open time to expire If the push button is connected to the active leaf the 1 leaf hold open time is used for 1 leaf applications and for 2 leaf applications the 2 le...

Page 61: ...closes and locks The contact sensors KI and KA are hidden The safety sensors and the obstacle detection remain active The door remains closed as long as the emer gency lock signal is applied to the input P KI activation NO Additional contact sensors P KI P KA For connection of addi tional normally open contacts P KA activation NO Switch function NO see PE1 Switch function OHZ NO see PE1 Stop 12 kO...

Page 62: ...leaf door Active leaf contact to GF control passive leaf contact to SF control Emergency lock 20KOhm NO see PE2 P KI activation NO Additional contact sensors P KI P KA For connection of addi tional normally open contacts P KA activation NO Switch function NO see PE1 Switch function OHZ NO see PE1 Stop 12 kOhm NO For the connection of a stop push button with 12 kOhm terminating resistor Reset switc...

Page 63: ...ol determines a fault When maintenance is due the output is connected cyclically and the fault LED on the MPS flashes Warning signal The function is used to cyclically switch on off a signal transmit ter while the door is opening or closing Electric strike For the connection of an ad ditional electric strike closed lock The function is used to signal the door mode e g to a build ing control centre...

Page 64: ...or mode e g to a build ing control centre closed Not closed Open Off Night Exit only Automatic Hold open Light control see PA1 Day Night changeover see PA1 not used Maintenance due see PA1 Holding magnet GF For setting the holding magnet active leaf Holding magnet SF For setting the holding magnet passive leaf WC timeout To connect a lamp or a signal to signal when the 30 minute timer has expired ...

Page 65: ...V TOE 24 V TEST 24 V FAN 0 V MAG 0 V Internal values current position 23 current motor power Mot DCU800 0 0 A Voltages Mains on 24 V internal xy z V 24 V external xy z V Temperatures DCU800 41 degrees C M DCU800 45 degrees C Statistics Cycles total 0 Cycles Manu 0 Hours 1352 Hours Ser 112 Joch cycles 235 current conditions Inputs SI1 off SI3 off RM off KB off KI off KA off NA off LS off AU off DO ...

Page 66: ...SVN 1280 161711 Example 27 3 8 Standard values Name 1 Sub menu 2 Sub menu Explanation Standard values no yes Values are set to standard set tings Position WIO wall blank ing and opening angle are re tained Fault memory is deleted A teaching run and initialisation run are not necessary 27 3 9 Reset DCU8 Name 1 Sub menu 2 Sub menu Explanation Reset DCU8 no yes Fault memory is deleted Posi tion and o...

Page 67: ...nd the second digit how often the key has to be activated to release operation of the DPS Block parameters no yes Entering the password in control unit ST220 X X Change digit with or X X Confirm digit and change to next position with X X Abort with x Display of the current position by the asterisk under it X X After completing entry press to accept the password à à After 1 minute without a button ...

Page 68: ... the NA LS AU and DO modes of operation à à If no key is pressed in service mode for a period of 2 minutes the mode of operation automatically changes à à In service mode the door remains in operation in the current mode of operation not when teaching is activated 1 Menu DPS Parameter Setting values Explanation O T Opening time 03 04 06 25 in s Opening time with automatic opening Setting pursuant ...

Page 69: ...equired See chapter 5 1 the values for opening time and closing time refer to an opening angle of 90 TO Electric strike type 00 No electric strike 01 Working current Drive does not have closing force pressure in the closed position before opening 02 Fail safe 03 Motor lock 04 Working pressure Drive has closing force pressure in the closed position before opening 05 Static close pressure 06 Motor c...

Page 70: ...passive leaf has closed completely This value must be set in order to fulfil EN 16005 The value does not correspond to the time fl Passive leaf start range 00 10 95 in Start of the passive leaf at opening range of the active leaf refer enced to its maximum opening range aD Servo duration 00 20 in s Adjustable duration of the force support in servo mode aO Additional servo torque 00 50 in Nm Adjust...

Page 71: ...ter manual opening or after automatic opening with set automatic door closing mode Setting pursuant to the table in the Powerturn installation instructions Da Back check 10 12 20 25 50 60 80 Application of the back check referenced to maximum opening range manual opening e0 Adj opening angle 9 00 09 in degrees The value is only for fine adjustment The value is taught during the teaching run and th...

Page 72: ...pens and if switched on the passive leaf opens Active in every mode of operation when the door is not closed aa KA delay 00 90 in s 0 1 only active when the door is in a closed position Can be ad justed in steps of 0 1 e1 PE1 function 00 Not used 03 Switch over summer NO For the connection of a push button for the summer function 04 Switch over winter NO For the connection of a push button for the...

Page 73: ...h fire alarm torque is set for the duration 23 1 leaf opening In 2 leaf systems when the signal is active on the active leaf only 1 leaf is opened e2 Configurable input 2 00 Not used e3 Configurable input 3 01 MPS For connection of a mechanical programme switch 03 Switch over summer NO For the connection of a push button for the summer function 04 Switch over winter NO For the connection of a push...

Page 74: ...ED at the MPS The con tact closes if the control determines a fault When maintenance is due the output is connected cyclically and the fault LED on the MPS flashes 05 Warning signal The function is used to cyclically switch on off a signal transmit ter while the door is opening or closing 06 Electric strike For the connection of an additional electric strike 08 closed lock The function is used to ...

Page 75: ...active Reversing in the event of an obstacle within closing following manual opening not active 01 active Reversing in the event of an obstacle within closing following manual opening active pa Auto rev closing 00 not active Reversing in the event of an obstacle within closing following automatic opening not active 01 active Reversing in the event of an obstacle within closing following automatic ...

Page 76: ...voltage 07 07 Active leaf fire alarm Smoke detector active Jumper not inserted 10 1 0 Active leaf rotary transducer Collective fault rotary transducer Encoder model Rotary transducer displays fault Edge counter Error in identifying the rotary transducer edges Position check Rotary transducer position error Direction error Rotational direction of motor or rotary transducer is incorrect 11 11 Motor ...

Page 77: ...ion PE1 Expected configuration as MPS Sabotage Stop emergency lock 36 3 6 Permanent activation PE2 Expected configuration as MPS Sabotage Stop emergency lock 37 37 Permanent activation KI Movement detector defective or activation 4 min 38 3 8 Permanent activation PE3 Expected configuration as MPS Sabotage Stop emergency lock 39 3 9 Permanent activation KA Activation longer than 4 min 40 4 0 Perman...

Page 78: ...otor defective 73 73 Permanent activation Collective fault permanent activation SF inputs 74 7 4 Rotary transducer SF Rotary transducer signals faulty 75 7 5 DCU800 hot Passive leaf drive motor or control temperature higher than 95 C 76 7 6 Sensor motor SF Motor temperature sensor defective 77 77 Passive leaf T sensor Control temperature sensor is defective 78 7 8 Overtemp SF Motor or control temp...

Page 79: ...UFO NT 79 ...