UFO-NT
14
"Open" and "close" safety sensor
5.2.3 Monitoring closing
1
SIS
11
1
GND
4
24VSENS
10 TST
SIS
-UB
+UB
COM
+
SIO
60 mA
Test
SIS
GC 342
BGS
BN
GN
YE
WH
PK
GY
BU
RD
1
Door transmission cable
DCU8 settings
X
Setting the "Contact type" parameter:
à
DPS:
Set
s1
to
0 2
("NC") (default setting).
à
ST220: Set the "Input signals", "SI1 – terminal SIO", "SI1 contact type" to "NC” (default setting).
X
Setting the Function parameter:
à
DPS: Set
f1
to the desired function.
à
ST220: Set the "Input signals", "SI1 – terminal SIS", "SI1 function" to the desired function.
5.3 Safety sensor GC 334
à
GC 334 module, mat. no. 126410
à
Follow the installation instructions
à
Accessories:
à
Interface GC 334, mat. no. 128306
à
Spot finder, mat. no. 112321
X
Setting the testing:
à
DPS: Set
Te
to
0 2
(testing with GND).
à
ST220: Set "Output signals", "Testing SI" to "Testing with GND".
à
Max. 6 modules in series
5.3.1 Monitoring closing and opening
X
Setting the "Contact type" parameter:
à
DPS:
Set
s1
to
0 2
(NC) and
s3
to
0 2
(NC) (default setting).
à
ST220: Set the "Input signals", "SI1 – terminal SIS1",
"SI1 contact type" to "NC" and
"SI3 – terminal SIO1", "SI3 contact type"
to "NC"(default setting).
X
Setting the Function parameter:
à
DPS: Set
f1
to the desired function and
f3
to
0 5
(SIO stop) or
0 6
(SIO stop SF GF).
à
ST220: Set the "Input signals", "SI1 – terminal
SIS1", "SI1 function" to the desired func-
tion and "SI3 – terminal SIO1", "SI3 func-
tion" to "SIO stop" or "SIO stop SF GF".
à
Configuration of the GC 334 modules on the
à
Hinge side:
DIP1 = ON
à
Opposite hinge side: DIP1 = OFF
SIS
1
GND
11 SIS
10 TST
4
24VSENS
1
GND
13 SIO
10 TST
4
24VSENS
SIO
VT
PK
GC 334 BS
WH
YE
BN
-
+
GN
BU
-
+
RD
GC 334 Module BS
GC 334 Module BGS
60mA
1
1
Door transmission cable