UFO-NT
15
"Open" and "close" safety sensor
5.3.2 Monitoring opening
X
Setting the "Contact type" parameter:
à
DPS: Set
s3
to
0 2
(NC) (default setting).
à
ST220: Set the "Input signals", "SI3 – terminal
SIO1" and "SI3 contact type" to "NC"
(default setting).
X
Setting the Function parameter:
à
DPS: Set
f3
to
0 5
(SIO stop) or
0 6
(SIO stop
SF-GF).
à
ST220: Set the "Input signals", "SI3 – terminal
SIO1" and "SI3 function" to "SIO stop" or
"SIO stop SF GF".
à
GC 334 module configuration: DIP1 = ON
1 GND
13 SIO
10 TST
4 24VSENS
SIO
GC 334 BS
WH
YE
BN
-
+
GN
BU
-
+
RD
GC 334
Module
60mA
1
PK
VT
1
Door transmission cable
5.3.3 Monitoring closing
X
Setting the "Contact type" parameter:
à
DPS: Set
s1
to
0 2
(NC)
(default setting).
à
ST220: Set the "Input signals", "SI1 – terminal
SIS1" and "SI1 contact type" to "NC"
(default setting).
X
Setting the Function parameter:
à
DPS: Set
f1
to the desired function.
à
ST220: Set the "Input signals", "SI1 – terminal
SIS1" and "SI1 function" to the desired
function.
à
GC 334 module configuration: DIP1 = OFF
1 GND
11 SIS
10 TST
4 24VSENS
SIS
GC 334 BGS
WH
YE
BN
-
+
GN
BU
-
+
RD
GC 334
Module
60mA
1
PK
VT
1
Door transmission cable