UFO-NT
17
"Open" and "close" safety sensor
5.4.1 Monitoring closing and opening
X
Setting the "Contact type" parameter:
à
DPS: Set
s1
to
0 2
(NC) and
s3
to
0 2
(NC) (default setting).
à
ST220: Set the "Input signals", "SI1 – terminal SIS1", "SI1 contact type" to "NC" and
"SI3 – terminal SIO3", "SI3 contact type" to "NC" (default setting).
X
Setting the Function parameter:
à
DPS: Set
f1
to the desired function and
f3
to
0 5
(SIO stop) or
0 6
(SIO stop SF GF).
à
ST220: Set the "Input signals", "SI1 – terminal SIS1", "SI1 function" to the desired function and
"SI3 – terminal SIO1", "SI3 function" to "SIO stop" or "SIO stop SF GF".
GC 335
Slaves
1
GND
13
SIO
10
TST
4
24VSENS
GC 335 Master
BGS
SIO
1
GND
11
SIS
10
TST
4
24VSENS
SIS
WH
BN
GY
GN
PK
YE
6
5
4
3
2
1
60mA
-
+
Test
GC 335 Master
BS
6
5
4
3
2
1
60mA
-
+
Test
1
2
3
4
5
6
7
8
9
10
-
+
Test
GC 332
Adapter
WH
BN
GY
GN
PK
YE
GC 335
Slaves
1
1
Door transmission cable