UFO-NT
32
Configurable outputs
12.2.5 Electric strike
à
The electric strike function is not permissible if the drive is used for the fire protection area (Powerturn F, F/R,
F-IS with fire protection kit).
à
Only inductive DC electric strikes (without integrated electronics) may be connected to PA2. Electric strikes
with integrated electronics must be connected to the configurable output PA1, see chapter 12.1.5, "Electric
à
The function is used to activate an additional open-circuit or fail-safe electric strike.
à
The contact closes or opens as soon as the door drive is activated.
à
Setting the parameters with
à
DPS: Set
a2
to
0 6
(Electric strike).
Set
TO
to the connected electric strike type, see chapter 27.5 "Service menu DPS".
à
ST220: Set "PA2 function" to "Electric strike".
Set "Electric strike type" to the connected electric strike type, see chapter 27.3 "Service menu
Drive-side supplied electric strike
1
Free swing diode 1N4007, mat. no. 115293
1
GND
1
2
24V
55 PA1A
56 PA1B
PA
PA2
57
Bolt message (RM)
See chapter 13 "Electric strike", "Bolt message".
12.2.6 Door status message
à
The function is used to signal the door status, e.g. to a customer building control centre.
à
Door modes:
08 Closed and locked
09 Closed
10
Not closed
11 Open
12 Off
13 Night
14
Exit only
15 Automatic
16
Hold open
20
Maintenance due
à
Set the parameters with:
à
DPS: Set
a2
to the desired message function.
à
ST220: Set "PA2 function" to the desired message function.
à
Connecting a building control centre, see chapter 12.2.2, "Fault".
12.2.7 Day-night changeover
à
The function is used to signal Day mode of operation to a customer building control centre.
The output switches to GND, if the mode of operation LS, AU 1-leaf, DO, or AU 2-leaf is set.
à
Connect a 24 V DC relay, mat. no. 103352, as electrical isolation.
à
Set the parameters with:
à
DPS: Set
a2
to
1 8
("Day/Night" mode of operation message).
à
ST220: Set "PA2 function" to "Day/Night changeover”.
à
Connecting a building control centre, see chapter 12.2.2, "Fault".