UFO-NT
34
Electric strike
à
ST220: Set “Door parameters”, “Opening delay day” or “Opening delay night” to the required time.
The electric strike signal is activated until the entire opening position and over the hold-open time. After the
hold-open time has expired and after a closure of approx. 10°, the electric strike signal is deactivated.
13.1 24V DC electric strike supplied on drive side
GEZE electric strike for standard applications, doors with access control
GEZE electric strike
type
Mat. no. Current consump-
tion
Voltage
Functions
A5000--B
144590 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or
24 V DC ±15 %
Instantaneous operation: 12–48 V AC/
DC
Fail-secure electric strike,
standard applications, doors
with access control
A5000-FB
with lock latch
guide
144632 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or
24 V DC ±15 %
Instantaneous operation: 12–48 V AC/
DC
Fail-secure electric strike,
standard applications, doors
with access control
A5300--B
144631 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or
24 V DC ±15 %
Fail-secure electric strike,
standard applications
A5000--E
145182 200 mA (at 8–11 V)
50 mA (at 12-24 V)
Continuous operation: 8–28 V DC
Instantaneous operation: 8-28 V AC/
DC
Fail-secure electric strike,
standard applications,
opening under sideload
with direct voltage
A5001--B
with switch contact
145183 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or
24 V DC ±15 %
Instantaneous operation: 12–48 V AC/
DC
Fail-secure electric strike,
standard applications, doors
with access control
GEZE electric strike for fire protection doors
GEZE electric strike
type
Mat. no. Current consump-
tion
Voltage
Functions
FT500--B
144634 200 mA (at 12 V)
100 mA (at 24 V)
Continuous operation: 12 or
24 V DC ±15 %
Instantaneous operation: 12–48 V AC/
DC
Fail-secure electric strike,
fire protection doors
FT501--E
with switch contact
144647 200 mA (at 8–11 V)
50 mA (at 12-24 V)
Continuous operation: 8–28 V DC
Instantaneous operation: 8-28 V AC/
DC
Fail-secure electric strike,
fire protection doors, open-
ing under sideload with
direct voltage
à
Max. current consumption of 1000 mA, but pay attention
to the total current consumption of all the components,
especially for sfail-safe electric strikes.
à
Working current electric strike for Powerturn:
à
IQ eStrike A5000--E, mat. no. 145182
à
Fail-secure
electric strike for Powerturn:
à
IQ eStrike A5300--B, mat. no. 144631
X
Mount a free swing diode 1N4007 (1), mat. no. 115293
(no free swing diode is required for GEZE electric strikes).
1
2
GND
1
2
24V
31
TOEA
32
TOEB
TOE
RM
33
1
Free swing diode
2
Wire jumper
13.2 Customer-supplied 12 V AC electric strike
Contact load output PA1 at 12 V AC: max. 1 A
~ 12V AC ~
max. 1A
GND
1
2
24V
31 TOEA
32 TOEB
TOE
RM
33