UFO-NT
55
Service menu
Name
1 Sub-menu
2 Sub-menu
Explanation
Closed position force Value:
00
N
min 00 N
max 150 N
Force activates in the closed
position after the end of the
latching action. Manual passing
is more difficult during the set
time. The higher the set force,
the longer the duration.
Examples: at 10 N = 0.5 s,
at 150 N = 2 s
Door closing torque
Value:
0
Nm
min 0 Nm
max. 70 Nm
Door closing torque time after
manual opening.
0 … 40:
41 … 70:
or safety sensors
necessary.
Hold-open times
Push and Go
Value:
1
s
min
0 s
max.
60 s
Hold-open time during passage
with Push and Go.
Manual
Value:
1
s
min
0 s
max.
70 s
no
Hold-open time for manual
opening.
“No” corresponds to an un-
limited hold-open time, no
automatic closing.
2-leaf (Summer)
Value:
1
s
min
0 s
max.
60 s
With activation KI, KA
2-leaf Opening (AU-So)
Setting on GF control.
1-leaf (Winter)
Value:
1
s
min
0 s
max.
60 s
With activation KI, KA
1-leaf Drive (AU-Wi, AU-So)
2-leaf Opening (AU-So)
Setting on GF control.
Authorised contact
Value:
1
s
min
0 s
max.
60 s
For activation by KB.
Close delay GF
-> EN16005/DIN18650
min
0 s
0 s:
both leaves close simultane-
ously.
01 … 15 s:
The active leaf closes some time
after the passive leaf.
max 16 s
16 s:
Active leaf does not close until
after the passive leaf has closed
completely.
dyn extension
no
yes
When activated, the passage
frequency is taken into account
in the hold-open time. The door
does not close as fast when pas-
sage requirements are increased.
Reversing
Manual rev. closing
not active
active
Reversing in the event of an ob-
stacle within closing following
manual opening.
Auto rev. closing
not active
active
Reversing in the event of an ob-
stacle within closing following
automatic opening.