UFO-NT
63
Service menu
Name
1 Sub-menu
2 Sub-menu
3 Sub-menu
Explanation
1-leaf opening
NO
In 2-leaf systems, when the
signal is active on the active leaf
only 1 leaf is opened.
Display only for 2-leaf drives.
Mode of opera-
tion push button
current state
Mode of operation
push button
Z-> not active
K-> NO contact
push button con-
tact
Not used
NO contact
Mode of operation push button
on the drive inactive.
Mode of operation push button
on the drive active.
Output sig-
nals
PA1
current state
PA1
Z-> not active
F->not used
K-> NO contact
PA1 function
Gong
If KA is triggered
Fault NO contact
The function is used for fault
messages, e.g. to a customer
building control centre. The
contact closes or opens respec-
tively if the control determines
a fault.
Fault NC
Fault MPS
The function is used to switch
the fault LED at the MPS. The
contact closes if the control
determines a fault. When
maintenance is due, the output
is connected cyclically, and the
fault LED on the MPS flashes.
Warning signal
The function is used to cyclically
switch on/off a signal transmit-
ter while the door is opening or
closing.
Electric strike
For the connection of an ad-
ditional electric strike
closed lock
The function is used to signal
the door mode, e.g. to a build-
ing control centre
closed
Not closed
Open
Off
Night
Exit only
Automatic
Hold open
Light control
The function is used to activate
a light controlling device which,
for example, switches on the
entry illumination as soon as
a contact sensor (KI, KA, KB,
SIS+KI, SIS+KA) is activated or
the door is opened manually.
Day/Night changeover
The function is used to signal
the day mode of operation to a
customer building control cen-
tre. The output switches to GND
if the mode of operation LS, AU
1-leaf, DO, or AU 2-leaf is set.
Maintenance due
The function is used to signal
the door mode, e.g. to a build-
ing control centre.
Holding magnet GF
For setting the holding magnet
(active leaf).