UFO-NT
69
Service menu
DPS Parameter
Setting values
Explanation
O ®
Hold-open times
1-leaf (winter)
00 …
01
… 10
12 … 20
25 … 50
60
in s;
with 2-leaf drive for winter operation. With activation KI, KA
f1
SIS function
01 SIS rev
If the safety sensor "close" triggers, the door reverses.
02 SIS and KI
If the safety sensor "close" triggers, the drive reacts as with activa-
tion KI.
03
SIS and KA
If the safety sensor "close" triggers, the drive reacts as for activa-
tion KA.
04
SIS and Stop
If the safety sensor "close" triggers, the drive stops.
f3
SI3 function
05 SIO Stop
If the safety sensor "open" triggers, only the drive on the detected
door leaf stops.
06 SIO Stop SF-GF
If the behaviour should be the same for active leaf and passive
leaf, both drives must be set to SIO stop SF GF. If the safety sensor
"open" triggers, both active leaf and passive leaf drive stop.
Te
Testing SI
00 No Testing
01
Testing with 24 V
02
Testing with GND
Testing the safety sensor. Depending on the type used, the test-
ing must be set to 24 V or GND here.
03
Energy-saving mode
To save energy, the Powerturn can automatically switch the GC
338 to standby mode if it is not required. See chapter 5.1.
*)
the values for opening time and closing time refer to an opening angle of 90°.
TO
Electric strike type
00
No electric strike
01
Working current
Drive does not have closing force (pressure in the closed position)
before opening.
02 Fail-safe
03
Motor lock
04
Working pressure
Drive has closing force (pressure in the closed position) before
opening.
05
Static-close pressure
06
Motor-close pressure
sT
Control type
80 DCU8
Only display, no setting option
81 DCU8-F
82 DCU8-Invers
oh
Type of installation
07 UFO-NT
UFA Underfloor operator
a T
Drive type
00
Spring force closes
01
Spring force opens
Ts
Door closer mode
00 Manual
01 Automatic
Manual: The door only closes with the set door closing torque
after manual opening, otherwise speed-controlled.
Automatic: The door always closes with the set door closing
torque regardless of the type of activation.
he
Manual intervention
00 not active
01 …10 active
Sets, within the automatic closing, the option to manually inter-
vene in the door movement from the SIO page. When active, the
door can then be manually reopened.
ep
Software version
e.g. SL, 10, 00 for DCU8 V1.0
or SF, 10, 01 for DCU8-F V1.0.1 for tailor-made solutions;
Scroll forwards using "arrow downwards", menu has 3 levels
1 Level
SL;
2 Level
10;
3 Level
00 (00 -> standard / 01
for customised solutions …).
N e