UFO-NT
71
Service menu
DPS Parameter
Setting values
Explanation
l2
Start teaching
->2 leaf Teaching
Start/terminate
Teaching a 2-leaf system For the procedure, see chapter 20.2.
e®
Current faults
ce
Displays the current errors in the fault memory.
Delete with
ce
.
O e
Delete old errors
ce
Displays the old errors in the fault memory. Delete with
ce
.
cp
Default setting
cP
Reset all the values to the default settings.
The state is the same as after the default setting. Values to
standard setting, fault memory, position and opening angle are
deleted. A teaching run and initialisation run are necessary.
lp
Standard values
dP
All values are set to the standard setting after acknowledge-
ment. Position and opening angle are retained. Fault memory is
deleted. A teaching run and initialisation run are not necessary.
pp
Reset DCU8
IP
After acknowledgement the display jumps to 88. Fault memory
is deleted. Position and opening angle are not deleted. The
processor restarts. A teaching run is not necessary, an initialisa-
tion run is necessary.
3 Menu
DPS Parameter
Setting values
Explanation
Os
Hold-open time KB
00 …
01
… 10
12 … 20
25 … 50
60
in s;
Hold-open time after activation with KB.
O D
dyn extension
00
no
01 yes
When activated, the passage frequency is taken into account in
the hold-open time. The door does not close as fast when pas-
sage requirements are increased.
s6
Manual closing time 05 … 06 …
15
… 25
in s;
Closing time after manual opening or after automatic opening
with set automatic door closing mode.
Setting pursuant to the table in the Powerturn installation
instructions.
D a
Back check
10 … 12 … 20 … 25 …
50
…
60 … 80
Application of the back check, referenced to maximum opening
range (manual opening).
e0
Adj.opening angle
–9
… 0
0
…
09
in degrees;
The value is only for fine adjustment. The value is taught during
the teaching run and then corresponds to point 0. This allows it
to be adjusted manually and, again, subsequently corresponds
to point 0. The opening value can thus be manually adjusted
step-by-step. Is not set in the default setting.
cl
Reversing limit
00 …
30
… 90
In 0.1 degrees of the drive axle.
Angle on the drive axle to fine-tune the tolerance in the closed
position from which the drive attempts to close again.
X
Set the value so that the door gap is as small as possible
before the drive closes again.
o2
Free swing function
00
no
01 yes
For doors without external loads such as wind or pressure, the
parameter “free swing function” can be activated in order to
enable optimum passage of the door.
ol
Move towards open
00
no
In the event of further opening attempts, the drive stops before
the obstacle in the opening range
01 Obstacle
Motor on
Drive pushes against the obstacle and turns motor off.
02 Obstacle
Motor off
Drive pushes against the obstacle and leaves motor on.
ef
Number of leaves
01
1-leaf Drive
02
2-leaf active
03
2-leaf Passive
Parameter sets which of the door leaves the drive is installed on.
s1
SI1 contact type
00
Not used
02 NC
04 Frequency
Parameter sets the use of the safety sensor "close" contact type.