UFO-NT
73
Service menu
DPS Parameter
Setting values
Explanation
11
Switch function OHZ
NO On activation, the output of the push button is closed. With
2-leaf assemblies the push button can be connected to the ac-
tive leaf control or to the passive leaf control. If the push button
is connected to the passive leaf control, both door leaves open
and close on activation of the switch function, even if the pas-
sive leaf control is switched off (bed opening). When the push
button is pressed once, the drive opens the door and closes
after the hold-open time has expired. When the push button is
pressed again (within the hold-open time) the drive closes the
door without waiting for the hold-open time to expire.
If the push button is connected to the active leaf, the 1-leaf
hold-open time is used for 1-leaf applications and for 2-leaf ap-
plications the 2-leaf hold-open time is used.
13
Reset switch
NO For restarting the drive. For the function, see chapter 27.3.9.
14
Double push button NO Open 1× press = 1 leaf open
Open 2× press = 2 leaf open
15
Stop NO
NO For connection of a stop push button
16
Stop NC
NC
19
Closed position SF
closed position contact for the passive leaf for 1-leaf door with
manual passive leaf (door closer):
21
WC control
Connection of the internal button
for the WC function.
22
Fire alarm
NO If active, the door opening torque function with fire alarm
torque is set for the duration.
23
1-leaf opening
In 2-leaf systems, when the signal is active on the active leaf only
1 leaf is opened.
e2
Configurable input 2
00 Not used
e3
Configurable input 3 01 MPS
For connection of a mechanical programme switch
03
Switch over summer NO For the connection of a push button for the summer function.
04
Switch over winter
NO For the connection of a push button for the winter function
Only for switching over from open 1-leaf to 2, not for actually
opening the door.
05 Sabotage
NC Permanently switched. If the contact is interrupted KB is not
evaluated in the mode of operation "night-time". All other func-
tions remain the same.
06
Closed position GF
NO Closed position contact for the door leaf
à
For 1-leaf door
à
For 1-leaf door drive with manual passive leaf (door closer):
Closed position contact for the active leaf
à
For 2-leaf door:
Active leaf contact to GF control; passive leaf contact to SF
control
07
Emergency lock.20 KOhm
NO
The input can be used to connect an
emergency lock switch.
When the emergency lock switch is activated,
the contact is closed and
24 V are applied to the input. The door closes
and locks. The contact sensors KI and
KA are hidden. The sensor strips
and obstacle detection
remain active. The door remains closed
as long as the emergency lock signal
is applied to the input.
08
P-KI activation
NO Additional contact sensors (P-KI, P-KA).
For connection of additional normally open contacts
09
P-KA activation
NO
10
Switch function
NO see PE1
11
Switch function OHZ
NO see PE1