UFO-NT
77
Fault messages ST220 and DPS
Fault no. Message
on the DPS
Message on the ST220
Fault description
23
2 3
Mechanical fault SF
A mechanical fault has occurred at the passive leaf; collective fault.
Rotate angle
A cam skip has been detected.
Defective magnetic valve
The solenoid valve of the energy store is defective.
25
2 5
Teaching run fault GF
Teaching run collective fault, teaching run invalid.
Latching action switch
Teaching run invalid, e.g. incorrectly set latching action switch.
Obstacle teach close
Obstacle of the door leaf during the teaching procedure.
Teaching time- out
Time-out expired within 60 s of teaching.
26
2 6
Teaching run fault SF
Passive leaf teaching run collective fault, teaching run invalid.
Latching action switch
Teaching run invalid, e.g. incorrectly set latching action switch.
Obstacle teach close
Obstacle of the door leaf during the teaching procedure.
Teaching time- out
Time-out expired within 60 s of teaching.
28
2 8
Relay DCU800
Motor relay defective.
29
2 9
SIO SF fault
Safety sensor “open passive leaf, collective fault”.
Permanent activation
Safety sensor “open passive leaf” activated for more than 4 min.
Testing
Error in testing safety sensor “open passive leaf”.
32
3 2
Sabotage
Sabotage active.
35
3 5
Permanent activation PE1
Expected configuration as MPS, Sabotage, Stop, emergency lock.
36
3 6
Permanent activation PE2
Expected configuration as MPS, Sabotage, Stop, emergency lock.
37
37
Permanent activation KI
Movement detector defective or activation > 4 min.
38
3 8
Permanent activation PE3
Expected configuration as MPS, Sabotage, Stop, emergency lock.
39
3 9
Permanent activation KA
Activation longer than 4 min.
40
4 0
Permanent activation KB
Activation longer than 4 min.
41
41
SIO 1
Safety sensor “open active leaf, collective fault”.
Permanent activation
Safety sensor “open active leaf” activated for more than 4 min.
Testing
Error in testing safety sensor “open active leaf”.
42
4 2
Emergency lock
Activation active
If the function is active via PE.
Push button defective
If the push button for the function was recognised as defective.
44
4 4
Input stop
Stop is active.
45
4 5
Motor hot
Motor or control temperature higher than 95 °C.
46
4 6
Motor T-sensor
Motor temperature sensor defective.
47
47
Control T-sensor
Control temperature sensor is defective.
48
4 8
Overtemp
Motor or control temperature higher than 105 °C.
51
51
24 V missing SF
Control defective passive leaf.
53
53
230 V error SF
230 V passive leaf collective fault.
230 V low voltage
230 V low voltage SF.
230 V high voltage
230 V high voltage SF.
54
5 4
Comm. DPS NT
Communication error DPS NT.
57
57
Fire alarm SF
Smoke detector active passive leaf.
60
6 0
Ctrl. DCU800
Internal control fault, collective fault for active leaf.