Configurable inputs
11.10 STOP
Configurable inputs PE1, PE2 and PE3 can be used for connection of a stop push button or sensor strip. Inputs
PE2 and PE3 can also be evaluated in the same way.
à
On activation, the door leaf stops (in case of 2-leaf systems both leaves) and remains in the stopped position
as long as the input is active.
à
In the case of 2-leaf systems, the stop push button can be connected to the active leaf control or to the pas-
sive leaf control.
à
To operate the DPS DPS see chapter 27.4 "DPS (DPS)".
à
To operate the service terminal ST220 see chapter 27.1 "Service terminal ST220".
The state of the drive to which the ST220 is connected is displayed.
X
Press the
button.
X
Select "Active leaf para" or "Passive leaf para" using the
or
key and press the
key.
For further settings see the description below.
For PE1, PE2, PE3:
à
Set the Contact type parameter with:
à
DPS:
Set
e1
,
e2
or
e3
to
1 5
(NO contact, not monitored) or to
1 6
(NC, not monitored).
à
ST220: Set "Signals", "Input signals", "PE1 function", "PE2 function" or "PE3 function" to "Stop NC" or "Stop NO".
52 PE2
oder
53 PE3
oder
51 PE1
2 24V
STOP
E1 = 15
E1 = 16
For PE2 or PE3:
à
In order to ensure protection of persons as specified in DIN 18650 / EN 16005, a 12 k or 20 k terminating
resistor must be connected to monitor the input. The terminating resistor must be directly connected to the
switch contact.
à
Set the Contact type parameter with:
à
DPS:
e2
or
e3
to
1 2
or
2 0
.
à
ST220: Set "Signals", "Input signals", "PE2" or "PE3", "PE2 function" or "PE3 function" to "Stop 12 kOhm" or
"Stop 20 kOhm".
12 k
Ω
oder
20 k
Ω
E2, E3 = 12 (Stop 12 k
Ω
-> NO)
E2, E3 = 20 (Stop 20 k
Ω
-> NO)
52 PE2
2 24V
PE2
PE3
oder
53 PE3
2 24V
11.11 Closed position detection
11.11.1 Closed position door leaf
(passive leaf drive, active leaf drive)
Feedback from a door contact attached in the closed position, connected to PE1, PE2, or PE3 of the control. The
door contact closes once the door leaf associated with the drive has reached the closed position.
Setting the parameters with
à
DPS: Set
e1
,
e2
or
e3
to
0 6
(closed position GF).
à
ST220: Set "PE1 function", "PE2 function" or "PE3 function" to "closed position GF".
11.11.2 detection passive leaf for 2-leaf doors with manual passive leaf
à
Feedback from a door contact of the passive leaf attached in the closed position, connected to PE1, PE2, or PE3.
The door contact closes once the passive leaf has reached the closed position.
à
Feedback from a door contact attached in the closed position, connected to PE1, PE2, or PE3.
The door contact closes once the door leaf has reached the closed position (passive leaf).
à
Setting the parameters with
à
DPS: Set
e1
, e2 or
e3
to
1 9
(closed position SF).
à
ST220: Set "PE1 function", "PE2 function" or "PE3 function" to "closed position SF".