UFO-NT
35
Free cable connections
13.3 Bolt message
When active, the DPS switches to night mode.
An operating mode LED on the drive indicates the operating mode (e.g. green when in automatic operating
mode).
à
Input RM blocks the activation of the drive when the door is locked. If Input RM becomes active while the door
is open, the door reverses and remains open.
à
If a further electric strike is connected with
à
Normally opened contact: Circuit the contacts in parallel.
à
NC contact: Switch the contacts in series.
à
Set the parameters with:
à
DPS:
Set
®®
to
01
(NO contact) or
0 2
(NC).
à
ST220: Set the "Signals", "Input signals", "Bolt contact type", "Bolt contact type" to " NO contact " or "NC".
à
When the bolt feedback signal is present, bolt the drive remains in its set operation mode but the DPS
switches its own state to “night”.
GND
1
2
24V
31
TOEA
32
TOEB
TOE
RM
33
GND
1
2
24V
31
TOEA
32
TOEB
TOE
RM
33
Normally opened
NC contact
13.4 Activation delay for lock switch contact
If a lock switch contact is used and “no electric strike” or “not used” is selected, the drive opens the door after a
valid activation only after 2.5 s if the system has switched from “locked” to “unlocked”.
14 Free cable connections
Up to 4 signals can be transmitted via the ribbon cable between connection board DCU802 and control board
DCU800 using the free cable connections. For example, this is prudent if devices are installed in the attachment
or intermediate cover and need to be connected to the connection board.
à
Max. signal voltage: 30 V AC/DC
à
Max. signal current: 0.3 A
57 56 55 2 1
98 97 96 95
13
36 35 1
33 32 31 2 1
N.N.
TOE
12
GND
24V
12
GND
24V
DCU800
DCU802
DCU802
DCU800
1
2
1
Internal ribbon cable
2
FREE