background image

 
The technical data are not binding and not expressly  
warranted characteristics of the goods. They are  
subject to change. Our General Conditions of Sale apply. 
Using the positioner, the instruction manual of the electric  
actuator type EA25-250 must be observed. 

 

Intended use 

Accessory board Positioner 

The positioner can be used with the electric actuators type EA25, EA45, EA120 
and EA250, both with the 24V AC/DC as well as the 100-230V AC version. The 
board is to be plugged into the housing of the actuator in the provided slots. 

 

Description 

Technical data 

Code 

Positioner 

Inputs with galvanic isolation 

199 190 603 

 

 

 

 

 

1

 

Function 

The positioner controls a user-defined valve position proportional to a given 
setpoint value. This can be 0 – 10 V or 4 – 20 mA. Feedback on the valve 
position (actual value) is done via the integrated 4 – 20 mA position detection. 
All signals can be inverted in any desired combination. 

 

 

 

The inputs are galvanically isolated, so the power supply does not have to 
be galvanically separated. 

 

Additionally the monitoring card module „Motor current monitoring“ is located 
on the positioner (left BCD switch). See chapter 6 „Settings motor current 
monitoring“ for further settings. 

 

2

 

Assembly of the positioner board 

 

 

 

Disconnect the actuator from the supply voltage. 

 

 

1.

 

Remove housing cover of the electric actuator (loosen the 4 screws, open 
cover). 

2.

 

Take the positioner board out of the packaging and check for damages. 

 

 

 

Do not touch the board itself. Electrostatic discharge can damage the 
components. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

3.

 

Insert the board vertical on the backside of the main board onto the red plug. 

 

 

 

Ensure that the board sits in the lateral guides and snaps.  

 

4.

 

Stick scheme label into the housing cover. 

5.

 

Set signal configuration and if necessary, motor current monitoring (see 
chapter 4 „Signal configuration“ and 6 „Settings motor current monitoring“). 
 

3

 

Connecting the positioner and test functioning 

Connect set point 4 – 20 mA (or 0 – 10 V) to terminals of the positioner, see 5 
„Terminal assignment“. Move actuator in positions OPEN and CLOSE, adjust 
positions if necessary: set 4 mA (0 V) for CLOSE and 20 mA (10 V) for OPEN. 
For general power supply in the positioner mode one of the power terminals 
needs to be energized (1 or 2). 

 

6.

 

Put the cover back in place and fasten it with the 4 screws. 

 

4

 

Signal configuration 

The signal configuration is performed via the right BCD-switch „Mode“, 
depending on switch position, the following signal configuration can be 
achieved:

 

 

BCD 

Input 

Output 

0 (factory setting) 

4-20 mA 

4-20 mA 

0-10 V 

4-20 mA 

4-20 mA (inverted) 

4-20 mA 

0-10 V (inverted) 

4-20 mA 

4-20 mA 

4-20 mA (inverted) 

0-10 V 

4-20 mA (inverted) 

7 (only as feedback) 

4-20 mA 

8 (only as feedback) 

4-20 mA (inverted) 

 
If the feedback is not connected the error LED will show an actual value error. This can be 
avoided by placing a resistor (supplied) between terminal 5 and 6 of the positioner. 
Remove the resistor to use the feedback. 

5

 

Terminal assignment 

The cables are applied as follows via a plug (according to signal configuration): 
 

 

4-20 mA  Ground 

0-10V 

Ground 

4-20 mA 

Ground 

IN 

OUT 

 

 

 

 
 
 

 

GF Piping Systems 

 

 

 

Instruction Manual 

 

 

Electric actuators type EA25-250: Positioner 
 

 

 

 

 
 

 
 
  Georg Fischer Piping Systems Ltd CH-8201 Schaffhausen  
  Phone +41 (0)52 631 30 26 / info.ps@georgfischer.com / www.gfps.com  

  700 278 095 
  GFDO_6429_4a (04.16) 
  © Georg Fischer Piping Systems Ltd 

  CH-8201 Schaffhausen/Switzerland, 2016                                                                               

 

 

 

 

 

 

 

 

   