HD50CR-AS
- 18 -
V1.1
Coils
- Read/Write parameters
Address
Type
Coil description
0
b
Receiving mode after transmission with Modbus protocol:
0=violate protocol and go in receiving mode right after transmission
1=respect protocol and wait 3.5 characters after transmission
1
b
Logging status: 0=active, 1=inactive
2
b
Logging mode: 0=non cyclic, 1=cyclic
3
b
Set 1 to delete the device logging memory. Bit zeroing is automatic.
9
b
Protection of configuration with password: 0=no, 1=yes
Changing the parameter requires the Administrator password (see Holding
Register 10036).
23
b
Enabling of the lower alarm threshold for the quantity #1:
0= disabled, 1= enabled
24
b
Enabling of the lower alarm threshold for the quantity #2:
0= disabled, 1= enabled
25
b
Enabling of the lower alarm threshold for the quantity #3:
0= disabled, 1= enabled
26
b
Enabling of the lower alarm threshold for the quantity #4:
0= disabled, 1= enabled
27
b
Enabling of the lower alarm threshold for the quantity #5:
0= disabled, 1= enabled
28
b
Enabling of the lower alarm threshold for the quantity #6:
0= disabled, 1= enabled
35
b
Enabling of the upper alarm threshold for the quantity #1:
0= disabled, 1= enabled
36
b
Enabling of the upper alarm threshold for the quantity #2:
0= disabled, 1= enabled
37
b
Enabling of the upper alarm threshold for the quantity #3:
0= disabled, 1= enabled
38
b
Enabling of the upper alarm threshold for the quantity #4:
0= disabled, 1= enabled
39
b
Enabling of the upper alarm threshold for the quantity #5:
0= disabled, 1= enabled
40
b
Enabling of the upper alarm threshold for the quantity #6:
0= disabled, 1= enabled
47
b
Enabling of the buzzer for the quantity #1: 0= disabled, 1=enabled
48
b
Enabling of the buzzer for the quantity #2: 0= disabled, 1=enabled
49
b
Enabling of the buzzer for the quantity #3: 0= disabled, 1=enabled
50
b
Enabling of the buzzer for the quantity #4: 0= disabled, 1=enabled
51
b
Enabling of the buzzer for the quantity #5: 0= disabled, 1=enabled
52
b
Enabling of the buzzer for the quantity #6: 0= disabled, 1=enabled
59
b
Enabling of the buzzer “Latch” function for the quantity #1:
0= disabled, 1=enabled
60
b
Enabling of the buzzer “Latch” function for the quantity #2:
0= disabled, 1=enabled
61
b
Enabling of the buzzer “Latch” function for the quantity #3:
0= disabled, 1=enabled
62
b
Enabling of the buzzer “Latch” function for the quantity #4:
0= disabled, 1=enabled
63
b
Enabling of the buzzer “Latch” function for the quantity #5:
0= disabled, 1=enabled
Summary of Contents for Delta OHM HD50CR-AS
Page 28: ...HD50CR AS 28 V1 1 NOTES...
Page 29: ...HD50CR AS 29 V1 1 NOTES...
Page 30: ...HD50CR AS 30 V1 1 NOTES...
Page 31: ......