16
5.1.9
Digital output connection
The GE552Y051 is equipped with two relays that can be used as digital outputs. You can connect a load to
them or use them to activate other systems. Outputs
O1
and
O2
can be controlled both remotely and via
web server (Ref. Chapter 11.1.10). For connection to electrical loads follow the model in Figure 10 and the
maximum values for each relay shown below:
- 5A@250Vac (Resistive Load)
- 5A@30Vdc (Resistive Load)
- 2A@250Vac (Inductive Load cosfi=0.4 ; L/R=7ms)
- 2A@30Vdc (Inductive Load cosfi=0.4 ; L/R=7ms)
Figure 10 - Digital output connection