13
Giacomini S.p.A.
Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia
consulenza.prodotti@giacomini.com
+39 0322 923372 - giacomini.com
Secondary circuit for DHW production
DHW PRODUCTION (Δ
t 35-30 °C)
PRIMARY CIRCUIT
WORKING CONDITIONS
FLOW RATE
[l/min]
FLOW RATE
[l/h]
POWER
[kW]
T INLET
[°C]
FLOW RATE
[l/h]
T OUTLET
[°C]
12
720
33
80
470
18,5
75
540
21,5
70
610
22
65
700
23
15
900
42
80
610
20,5
75
700
23
70
800
24
65
910
25
17
1020
47,5
80
710
22
75
810
24
20
1200
56
80
850
23
75
970
25
Hydraulic data for domestic water circuit
0,01
0,1
1,0
10,0
0,10
1,00
∆
p [bar]
Q [m
3
/h]
Kv = 2,1