Technical data
• Max. working temperature: 90 °C
• Max. working pressure:
- primary circuit: 10 bar
- DHW secondary circuit: 10 bar
- heating secondary circuit: 4,5 bar
• Temperature range of the secondary heating circuit:
- low temperature: 25÷45 °C
- high temperature: 25÷85 °C
• Temperature range of the secondary DHW circuit: 30÷60 °C (Set-Point 50 °C)
• Nominal flow rate on primary circuit:
850 l/h @ 80 °C for 56 kW
1030 l/h @ 80 °C for 67 kW
WARNING.
The satellite can be used in closed boiler rooms for operation
with non-aggressive fluids (water, glycol-based water in compliance with VDI
2035/ÖNORM 5195).
WARNING.
Max. working differential pressure for the primary side = 4 bar
(priority valve)
• G 3/4“F connections with adjustable tail pieces.
• Electronic thermoregulation with Set-point, to manage the DHW temperature and heating temperature.
• Remote control with chronothermostat function to manage the parameter (for single zone), with display.
• Multizone additional control by the free contact on the electronic board (additional thermostats to be ordered separately).
• External temperature probe for climatic compensation.
• Double heat exchangers in parallel configuration: heating and DHW production, with priority for DHW production.
• Flow switch for priority of DHW production.
• Expansion vessel, safety valve and high efficiency circulator (15/7), comply with ErP Directive (2009/125/EC).
• Motorized three-way priority valve on the delivery of the primary side.
• Motorized two-way modulating valve on the return of the primary side.
• Filter and manual air vent valve on the primary side.
• Safety pressure switch for low pressure on the primary side.
• Heat exchanger and fully insulated piping.
• Painted sheet metal cabinet (RAL9010), with key locking.
Main features
Versions and product codes
Completion codes
• GE552:
thermal energy meter
• GE552-2:
domestic water meters
• GE551Y135:
template with shut-off valves and Ø 22 mm system connections
• GE551Y136:
template with shut-off valves and 3/4”M system connections
• Data centralization components via M-Bus,
GE552-4 series
, or via Wireless M-Bus,
GE552-W series
PRODUCT CODE
HIU TYPE
HEATING SIDE
POWER
DHW HEAT EXCHANGER
NOMINAL POWER
TEMPLATE WITH VALVES
GE556Y413
Heating and DHW production
24,5 kW
56 kW
GE551Y135/GE551Y136
GE556Y416
Heating and DHW production
24,5 kW
67 kW
GE551Y135/GE551Y136
NOTE.
Remote control and external temperature probe included with HIU
NOTE.
Use energy meters approved in accordance with the standardized “flow disturbance elements” and provided for by the EN 1434 for null rectilinear section