background image

9

Giacomini S.p.A.

Via per Alzo 39, 28017 San Maurizio d’Opaglio (NO) Italia

 consulenza.prodotti@giacomini.com

 +39 0322 923372 - giacomini.com

Constant differential pressure Δp-c (I, II, III) [RECOMMENDED]

0

0

1

2

0

20

40

60

3

4

5

6

7

8

p-v (variabile)

0

10

20

30

40

50

60

70

80

0,5

1,0

1,5

2,0

3,0

4,0

3,5

2,5

0

0,5

1,0

1,5

2,0

3,0

4,0

3,5

2,5

Q [m

3

/h]

Q [m

3

/h]

P1 [W

]

H [m]

H [kP

a]

III 

II 

I

∆p-v 

max.

max.

III 

II 

I

0

0

1

2

0

20

40

60

3

4

5

6

7

8

p-c (costante)

0

10

20

30

40

50

60

70

80

0,5

1,0

1,5

2,0

3,0

4,0

3,5

2,5

0

0,5

1,0

1,5

2,0

3,0

4,0

3,5

2,5

Q [m

3

/h]

Q [m

3

/h]

P1 [W

]

H [m]

H [kP

a]

III 

II 

I

∆p-c 

max.

max.

III 

II 

I

0

0

2

0

20

40

60

4

6

8

10

Velocità costante (I, II, III)

0

10

20

30

40

50

60

70

80

0,5

1,0

1,5

2,0

3,0

4,0

3,5

2,5

0

0,5

1,0

1,5

2,0

3,0

4,0

3,5

2,5

Q [m

3

/h]

Q [m

3

/h]

P1 [W

]

H [m]

H [kP

a]

III 

II 

I

III 

II 

I

Setting the control mode

The  LED  selection  of  control 

modes and corresponding pump 

curves  takes  place  in  clockwise 

succession.

• Press the operating button briefly 
(approx. 1 second).

  LEDs  display  the  set  control 

mode and pump curve.

Air venting

• Fill and vent the system correctly.
If  the  pump  does  not  vent 
automatically:
•  Activate  the  pump  venting  function 
via  the  operating  button:  press  and 

hold for 3 seconds, then release.

 

The  pump  venting  function  is 

initiated and lasts 10 minutes.

 

The  top  and  bottom  LED  rows 

flash in turn at 1 second intervals.

 

To cancel, press and hold the 

operating button for 3 seconds.

• After venting, the LED display shows 
the previously set values of the pump.

Fault signals

• The fault signal LED indicates a fault.
• The pump switches off (depending on the fault) and attempts a cyclical restart.

LED

FAULTS

CAUSES

REMEDY

Lights up red

Blocking

Rotor blocked

Activate manual restart or

acontact customer service

Contacting/winding

Winding defective

Flashing red

Under/overvoltage

Power supply too low/high on mains side

Check mains voltage and 

operating conditions, and request 

customer service

Excessive module 

temperature

Module interior too warm

Short-circuit

Motor current too high

Flashing red/green

Generator operation

Water is flowing through the pump hydraulics,

but there is no mains voltage at the pump

Check the mains voltage,

water quantity/pressure

and the ambient conditions

Dry run

Air in the pump

Overload

Sluggish motor, pump is operated outside of its 

specifications (e.g. high module temperature).

The speed is lower than during normal operation

 Circulator features

Summary of Contents for GE556-6 Series

Page 1: ...th centralised heat production e g district heating The configuration with two heat exchangers in parallel provides the following advantages parallel and non intermittent handling of the domestic hot...

Page 2: ...l configuration heating and DHW production with priority for DHW production Flow switch for priority of DHW production Expansion vessel safety valve and high efficiency circulator 15 7 comply with ErP...

Page 3: ...DUCTION 10 Flow switch 11 Brass spacer for water meters 12 Check valve HEATING 13 Minimum pressure switch 14 Circulator 15 Pressure gauge 6 bar 16 Heat exchanger for heating function 17 Manual air ven...

Page 4: ...35 template with shut off valves and 22 mm system connections GE551Y136 template with shut off valves and 3 4 M system connections GE551Y136 Template with 7 valves connections from below GE551Y135 Tem...

Page 5: ...Safety valve Expansion vessel Manual air vent valve Circulator Heat exchanger Pressure gauge P P Minimum pressure switch Temperature probe F Flow switch Check valve E E Brass spacer for thermal energy...

Page 6: ...ing function the two way modulating valve controlled by the electronic management of the HIU restricts the flow demand from the primary to the minimum necessary to obtain the preset Set Point temperat...

Page 7: ...sh Turn the knob to select the desired value DHW Set point press key until the icon and the DHW set point value start to flash Turn the knob to select the desired value Kd this setting is only availab...

Page 8: ...WINTER and HEAT ONLY operating modes The function is enabled disabled by setting the t13 parameter via remote control Once activated it forces a request for operation in heating mode at a setpoint es...

Page 9: ...nting function is initiated and lasts 10 minutes The top and bottom LED rows flash in turn at 1 second intervals To cancel press and hold the operating button for 3 seconds After venting the LED displ...

Page 10: ...16 SAFETY THERMOSTAT K373 K373I REMOTE CONTROL K480Y002 MULTIZONE ADDITIONAL CONTROL EXTERNAL TEMPERATURE PROBE K365P 230 Vac WARNING Work on electrical components must be carried out by qualified pe...

Page 11: ...ry WARNING Flush all pipes before installing the HIU on the template WARNING Unused connections and ball valves must be closed with a cap WARNING Upon installation also include a filling circuit for t...

Page 12: ...2 80 150 30 75 170 30 70 175 30 65 210 31 60 260 32 LOW TEMPERATURE HEATING t 45 40 C PRIMARY CIRCUIT WORKING CONDITIONS CIRCULATOR SPEED FLOW RATE l h POWER kW T INLET C FLOW RATE l h T OUTLET C MAX...

Page 13: ...TION t 35 30 C PRIMARY CIRCUIT WORKING CONDITIONS FLOW RATE l min FLOW RATE l h POWER kW T INLET C FLOW RATE l h T OUTLET C 12 720 33 80 470 18 5 75 540 21 5 70 610 22 65 700 23 15 900 42 80 610 20 5...

Page 14: ...delivery C T primary return C 12 l min 15 l min 17 l min 20 l min Reduced flow rates requests to the primary in heating operation 65 70 75 80 T primary delivery C 600 700 800 900 1000 1100 1200 1300...

Page 15: ...250 42 65 310 42 60 400 42 HIGH TEMPERATURE HEATING t 60 45 C PRIMARY CIRCUIT WORKING CONDITIONS CIRCULATOR SPEED FLOW RATE l h POWER kW T INLET C FLOW RATE l h T OUTLET C MAX 1400 24 5 80 750 48 75...

Page 16: ...OW RATE l h POWER kW T INLET C FLOW RATE l h T OUTLET C 12 720 33 80 465 17 5 75 510 18 5 70 580 20 65 670 22 15 900 42 80 595 19 5 75 660 20 5 70 750 22 65 880 24 17 1020 47 5 80 700 21 75 770 22 70...

Page 17: ...C T primary return C 24 l min 12 l min 15 l min 17 l min 20 l min 22 l min Reduced flow rates requests to the primary in heating operation High temperature 65 70 75 80 T primary delivery C 600 700 80...

Page 18: ...water outlet D Primary inlet E Primary outlet F Heating return G Heating delivery X Fairleads Y Hole for safety valve drain Dimensions in mm HIU GE551Y135 TEMPLATE 460 55 60 325 845 60 60 60 60 60 45...

Page 19: ...ni com 39 0322 923372 giacomini com WRAS certification REF IN COMPONENTS PARAGRAPH COMPONENT CERTIFICATE NUMBER Gaskets 1509514 10 Flow switch 1605300 5 16 Heat exchanger 1909083 Reference Standards U...

Page 20: ...ates formes cologiques appropri es pour recevoir le produit pour sa destruction et son recyclage correct ult rieur Il convient galement de rappeler que en cas d achat d un appareil quivalent le distri...

Reviews: