Addressing

The addressing through microswitch with several ways is not relevant when 
K282 actuator is used as single device (stand-alone configuration): it is not 
necessary to make any configuration in this application.
The addressing through microswitch with several ways is vital for the correct 
configuration of the device in those applications in which the actuator is used 
in combination with KM20x network controller.
All microswitch sliders are positioned on “OFF” (side with 1-8 numbers) 
on delivery. K282 actuator uses selectors from 1 to 6 to assign an address 
between 0 and 31: check the address to assign on the design documentation 
of the system.

Signalling elements

The led on the frontal side of K282 actuator provides two kinds of information: 
the application type, stand-alone or with bus signal network connection to 
KM203 network controller and summer/winter mode set to regulate the 
delivery temperature.
Fixed red: indicates stand-alone functioning in WINTER mode.
Fixed green: indicates stand-alone functioning in SUMMER mode.
Flashing red: indicates the functioning in combination with KM203 network 
controller in WINTER mode.
Flashing green: indicates the functioning in combination with KM203 
network controller in SUMMER mode.
Flashing alternate red/green: indicates that K282 actuator, used in combination 
with KM203 network controller, is no more supervised by KM203 because of 
an anomaly (deactivation of supply to network controller or communication 
problems on bus network).
The operating set has become the one set on the rotating potentiometer and 
the real mode, that is the one imposed by the supervisor, is not coherent with 
the operating mode imposed by the manual selector on the frontal side. With 
this signal, it is recommended to check the correct supply to the network 
controller and the correct functionality of bus network.

When 24 V~ supply is activated to K282 actuator, the integrated electronic 
regulator starts a cycle of adjustment in which the stem of the actuator is 
led to complete by-pass position (the whole stem has gone back in the 
actuator body).

Connection to bus

Data between K282 actuator and KM203 network controller are transfered 
through the system bus (connection to primary bus) by using RT+, RT- and 
Com terminals. In addition, the supply for the communication function is 
carried through the system bus by using V and Com terminals. Max. 3 K282 
actuators can be connected to KM203 network controller.

1

2

3

4

6

7

8

2

1

1

2

1

2

3

4

6

7

8

1  Jumper for manual control (open ring) of the actuator

2  8 way microswitch for actuator addressing

SHUTOFF

K282X002

24V

50/60 Hz

5VA

SENSOR DELIVER

Y TEMP

.

BLU WHITE GREEN YELLOW

V Com R

T-

RT

+

GRA

Y

24V

BUS

BROWN

SHUTOFF PINK

Conductor color

Function

BROW

24 V~ supply connection

GRAY

24 V~ supply connection

Conductor color

Function

YELLOW

RT+ Signal (RS485 standard)

GREEN

RT- Signal (RS485 standard)

WHITE

Com Common ( supply)

BLUE

V SELV supply

Caution!

Before connecting K282 actuator, make sure that network tension IS 
NOT CONNECTED and that it corresponds to the one written on the 
back of the device (24 V~). The device must be installed by qualified 
staff only.

Caution!

Before the connection to the system bus, make sure that 
KM203 network controller is not supplied, not to damage the 
communication module of K282 actuator. In case more than 3 
actuators are connected to KM20x controller (through primary bus), 
it is necessary to provide a separated supply of the devices. The bus 
cable of K282 actuator must be placed in a canalization with an 
electrical protective covering independent from canalizations that 
carry network tension or that control actuators.

Position of microswitch ways

Ind.

1

2

3

4

5

6

0

OFF

OFF

OFF

OFF

OFF

OFF

1

ON

OFF

OFF

OFF

OFF

OFF

2

OFF

ON

OFF

OFF

OFF

OFF

3

ON

ON

OFF

OFF

OFF

OFF

4

OFF

OFF

ON

OFF

OFF

OFF

5

ON

OFF

ON

OFF

OFF

OFF

6

OFF

ON

ON

OFF

OFF

OFF

7

ON

ON

ON

OFF

OFF

OFF

8

OFF

OFF

OFF

ON

OFF

OFF

9

ON

OFF

OFF

ON

OFF

OFF

10

OFF

ON

OFF

ON

OFF

OFF

11

ON

ON

OFF

ON

OFF

OFF

12

OFF

OFF

ON

ON

OFF

OFF

13

ON

OFF

ON

ON

OFF

OFF

14

OFF

ON

ON

ON

OFF

OFF

15

ON

ON

ON

ON

OFF

OFF

16

OFF

OFF

OFF

OFF

ON

OFF

17

ON

OFF

OFF

OFF

ON

OFF

18

OFF

ON

OFF

OFF

ON

OFF

19

ON

ON

OFF

OFF

ON

OFF

20

OFF

OFF

ON

OFF

ON

OFF

21

ON

OFF

ON

OFF

ON

OFF

22

OFF

ON

ON

OFF

ON

OFF

23

ON

ON

ON

OFF

ON

OFF

24

OFF

OFF

OFF

ON

ON

OFF

25

ON

OFF

OFF

ON

ON

OFF

26

OFF

ON

OFF

ON

ON

OFF

27

ON

ON

OFF

ON

ON

OFF

28

OFF

OFF

ON

ON

ON

OFF

29

ON

OFF

ON

ON

ON

OFF

30

OFF

ON

ON

ON

ON

OFF

31

ON

ON

ON

ON

ON

OFF

Caution!

Make sure that the assigned address is correct: it is not possible 
to have two devices with the same address in the same system.

Summary of Contents for Giacoklima Series

Page 1: ...er winter switching has been made through selector position the rotating potentiometer at the desired set according to the appropriate graduated scale the scale working during the winter is indicated with red numbers range from 20 C to 60 C ascending clockwise the scale working during the summer is indicated with blue numbers range from 15 C to 25 C ascending anticlockwise Both controls are used i...

Page 2: ...tuator and KM203 network controller are transfered through the system bus connection to primary bus by using RT RT and Com terminals In addition the supply for the communication function is carried through the system bus by using V and Com terminals Max 3 K282 actuators can be connected to KM203 network controller 1 2 3 4 6 7 8 2 1 1 2 1 2 3 4 6 7 8 1 Jumper for manual control open ring of the act...

Page 3: ...en the rotating potentiometer is completely rotated anticlockwise the stem of the actuator is protruding 100 and the mixing valve opens the direct way completely when potentiometer is completely rotated clockwise For the manual positioning Remove 24 V supply to K282 actuator Loosen the actuator ring fixing to valve body and unscrew the actuator completely Remove the upper shell of the actuator by ...

Page 4: ...923 372 6 39 0322 923 255 consulenza prodotti giacomini com This pamphlet is merely for information purposes Giacomini S p A retains the right to make modifications for technical or commercial reasons without prior notice to the items described in this pamphlet The information described in this technical pamphlet does not exempt the user from following carefully the existing regulations and norms ...

Reviews: